BS 7671:2018+A2:2022 Compliant

Lighting Circuit Design Calculator

Calculate circuit capacity, cable sizing, voltage drop, and diversity for LED, CFL, fluorescent, and halogen lighting installations. Professional BS 7671 compliant tool for UK electricians.

Diversity & Control Gear

Apply BS 7671 diversity factors (domestic 66%, commercial tiered) and automatic control gear loss calculations for LED (10%), CFL/fluorescent (15%).

Cable Sizing & Voltage Drop

Automatic cable size recommendations from Table 4D5. Voltage drop compliance checking against 3% limit (Regulation 525) with detailed mV/A/m calculations.

Protection & Utilization

Verify Ib ≤ In ≤ Iz compliance (Regulation 433.1). Real-time circuit utilization monitoring with warnings at 80%, 90%, 95% thresholds. MCB type recommendations.

Circuit Configuration

Cable Details (Optional - for voltage drop calculation)

Lighting Fittings

Total: 8 fittings

80W

Important Disclaimer

This calculator is provided for informational and educational purposes only. While we strive for accuracy and compliance with BS 7671:2018+A2:2022 regulations, calculations should be verified by a qualified electrician.

Professional Verification Required: All electrical work must be designed, installed, tested, and certified by a competent person in accordance with BS 7671 (18th Edition) and Building Regulations Part P.

No Liability: London Electrical Distributors and its contributors accept no responsibility for any loss, damage, or injury arising from the use of this calculator. Results are estimates and may vary based on specific installation conditions, environmental factors, and local regulations.

Use at Your Own Risk: By using this tool, you acknowledge that electrical design and installation carries inherent risks and should only be undertaken by qualified professionals with appropriate insurance and certification.

How to Use This Calculator

Step 1: Configure Circuit Parameters

  • MCB Rating: Select 6A (domestic), 10A (standard), or 16A (heavy duty)
  • MCB Type: Type B for general lighting, Type C for LED/CFL with inrush, Type D for halogen
  • Installation Type: Domestic (66% diversity), Commercial (tiered), Industrial/Emergency (no diversity)
  • Apply Diversity: Enable to reduce design load per BS 7671 Appendix 1

Step 2: Add Cable Details (Optional)

  • Cable Length: Enter total run length in meters for voltage drop calculation
  • Cable Size: Leave as "Auto-recommend" or select specific size (1.0mm² - 10.0mm²)
  • Voltage drop will be calculated using BS 7671 Table 4D1B (mV/A/m values)

Step 3: Add Lighting Fittings

  • Fitting Type: Select LED, LED Panel, LED Downlight, CFL, Fluorescent, or Halogen
  • Wattage: Enter lamp wattage (control gear losses added automatically)
  • Quantity: Number of fittings of this type
  • Use quick-select buttons for typical wattages (e.g., 5W, 10W, 15W for LED)
  • Click "+ Add Fitting" to include different fitting types on same circuit

Step 4: Interpret Results

  • Load Summary: Connected load, with control gear, design load (after diversity), design current
  • Circuit Capacity: Utilization percentage with color-coded bar (green <80%, yellow 80-90%, orange 90-95%, red >95%)
  • Protection Compliance: Verifies Ib ≤ In ≤ Iz per Regulation 433.1
  • Cable Sizing: Recommended size, voltage drop (V and %), compliance status
  • Additional Capacity: How many more fittings (at average wattage) can be added
  • Warnings: Capacity issues, inrush current concerns, MCB type suitability
  • Recommendations: Circuit optimization, consolidation, emergency lighting reminders

Understanding Lighting Circuit Design

BS 7671 Protection Requirements (Regulation 433.1)

Every circuit must satisfy the fundamental protection equation: Ib ≤ In ≤ Iz

  • Ib (Design Current): The current the circuit is designed to carry under normal conditions
  • In (Nominal Current): The MCB rating (6A, 10A, or 16A for lighting)
  • Iz (Cable Capacity): The current-carrying capacity of the cable under installation conditions

This ensures the circuit can safely carry the design load, the MCB will protect against overload, and the cable won't overheat.

Diversity Factors (BS 7671 Appendix 1)

Diversity acknowledges that not all lighting circuits operate at full load simultaneously:

  • Domestic (66%): In homes, typically only 2 out of 3 lights are on at any time
  • Commercial (Tiered): Offices/shops have more predictable usage - first 10 outlets at 100%, next 10 at 75%, next 10 at 50%, remaining at 25%
  • Industrial (100%): Factories require full illumination during operation - no diversity
  • Emergency (100%): Must always be available - no diversity per BS 5266

Applying diversity reduces the design current, allowing more efficient MCB and cable sizing while maintaining safety.

Control Gear Losses

Modern lighting uses electronic drivers/ballasts that consume additional power:

  • LED (10% loss): A 50W LED panel draws 55W from the circuit due to driver efficiency
  • CFL & Fluorescent (15% loss): Electronic ballasts add approximately 15% overhead
  • Halogen (No loss): Simple resistive load, no control gear required

Always calculate circuit load using the total power drawn from the circuit, not just the lamp wattage.

Voltage Drop Limits (Regulation 525)

BS 7671 limits voltage drop to 3% of nominal voltage for lighting circuits (6.9V at 230V):

  • Excessive voltage drop causes dimming, flicker, and reduced lamp life
  • Calculate using: Voltage Drop (V) = (mV/A/m) × Current (A) × Length (m) ÷ 1000
  • Use larger cable sizes or shorten circuit runs to reduce voltage drop
  • mV/A/m values from Table 4D1B: 1.0mm² = 44, 1.5mm² = 29, 2.5mm² = 18, etc.

MCB Type Selection

MCB type determines the magnetic trip threshold:

  • Type B (3-5× In): General purpose, suitable for resistive loads and small numbers of LED/CFL
  • Type C (5-10× In): Recommended for circuits with many LED or fluorescent fittings (moderate inrush)
  • Type D (10-20× In): Required for halogen circuits (cold filament inrush up to 12× running current)

Using Type B with >20 fittings may cause nuisance tripping during switch-on due to cumulative inrush current. Consider Type C or stagger switching.

Emergency Lighting Requirements

BS 5266 requires:

  • Emergency lighting must be on a separate circuit from normal lighting
  • Minimum 1 lux illumination on escape routes
  • 3-hour battery backup minimum
  • No diversity factors - must assume all lights operating simultaneously
  • Regular testing and maintenance required (monthly function test, annual duration test)

Frequently Asked Questions

How do you calculate lighting circuit capacity?

Lighting circuit capacity is calculated by multiplying the MCB rating (In) by the supply voltage (230V) and applying diversity factors if applicable. For example, a 10A MCB provides 2,300W capacity. With domestic diversity (66% per BS 7671), the design capacity would be approximately 1,518W. The calculator considers total connected load, control gear losses (10-15% for LED/CFL), and diversity factors to determine if the circuit is within safe operating limits.

What diversity factors apply to lighting circuits?

BS 7671 Appendix 1, Section 1 specifies diversity factors for lighting installations. Domestic: 66% (assume only 66% of lights on simultaneously). Commercial: Tiered approach - first 10 fittings at 100%, next 10 at 75%, next 10 at 50%, remaining at 25%. Industrial/Emergency: No diversity (100%) - all lights must be able to operate simultaneously. Diversity reduces the design load and allows more efficient circuit design while maintaining compliance.

What are control gear losses in lighting circuits?

Control gear losses refer to power consumed by drivers, ballasts, and control equipment in addition to the lamp itself. LED fittings have approximately 10% losses (multiply by 1.1), while CFL and fluorescent fittings have 15% losses (multiply by 1.15). Halogen has no control gear (multiply by 1.0). For example, a 50W LED panel actually draws 55W from the circuit. This calculator automatically applies appropriate control gear factors based on fitting type to ensure accurate load calculations.

What cable size do I need for a lighting circuit?

Cable sizing must satisfy two criteria per BS 7671: (1) Current-carrying capacity (Iz) must be ≥ MCB rating (In) and design current (Ib), and (2) Voltage drop must be ≤ 3% (6.9V) of supply voltage. Typical sizes: 1.0mm² for domestic lighting (up to 13.5A), 1.5mm² for commercial (up to 17.5A), 2.5mm² for industrial/long runs (up to 24A). The calculator recommends the minimum size meeting both requirements and checks voltage drop compliance if cable length is provided.

Why does MCB type matter for lighting circuits?

MCB type determines the magnetic trip threshold for protection against short circuits. Type B (3-5× In) is standard for general lighting with low inrush. Type C (5-10× In) is recommended for LED and fluorescent circuits with moderate inrush from control gear. Type D (10-20× In) is for halogen circuits with very high cold-filament inrush (up to 12× running current). Using Type B with >20 fittings may cause nuisance tripping during switch-on. This calculator warns when MCB type may not suit the installation.