Cable Size Calculator - BS 7671 Compliant

Calculate the correct cable size for electrical installations according to British Standards BS 7671:2018+A2:2022

Calculate Cable Size

Enter your installation parameters to calculate the required cable size

Flat twin and earth cable with PVC insulationDomestic fixed wiring - lighting, sockets, cookers

Amps

The maximum current the circuit will carry

meters

One-way cable run distance from distribution board to load

How the cable will be installed (affects current carrying capacity)

How to Calculate Cable Size UK - Complete Guide

Calculating the correct cable size for UK electrical installations requires consideration of several critical factors according to BS 7671 wiring regulations. This guide explains the complete process step-by-step.

Step 1: Determine the Design Current (Ib)

The design current is the maximum current your circuit will carry under normal operating conditions.

  • For known loads: Divide the power (watts) by voltage. Example: 9.5kW shower ÷ 230V = 41.3A
  • For socket circuits: Use the circuit breaker rating (e.g., 32A for ring main)
  • For motors: Check the motor nameplate for full load current

Step 2: Apply Correction Factors

BS 7671 requires cable sizing to account for installation conditions that affect heat dissipation:

Installation Method (Ca)

  • Clipped direct (Method C): Factor = 1.0 (best cooling)
  • In conduit on walls (Method B): Factor = 0.95
  • In thermal insulation (Method A): Factor = 0.5-0.89 (worst cooling)

Ambient Temperature (Cg)

Standard is 30°C. For loft spaces (45°C) or other hot environments, apply temperature correction from BS 7671 Table 4B1.

Grouped Circuits (Ci)

Multiple cables grouped together generate more heat. Correction factors from BS 7671 Table 4C1.

Step 3: Calculate Required Current Carrying Capacity (It)

Divide your design current by the overall correction factor:

It = Ib ÷ (Ca × Cg × Ci)

Example: 32A circuit, in conduit (0.95), at 30°C (1.0), with 2 cables (0.8):
It = 32A ÷ (0.95 × 1.0 × 0.8) = 42.1A required capacity

Step 4: Select Cable Size from BS 7671 Tables

Choose the cable size from the appropriate BS 7671 table based on your cable type and installation method:

  • Table 4D5: Twin and earth cables (most common domestic)
  • Table 4D4A: Steel wire armoured (SWA) cables
  • Table 4E4A: Single-core cables in conduit

Select the smallest cable size that has a current rating ≥ It (your calculated capacity)

Step 5: Check Voltage Drop

BS 7671 Regulation 525 limits voltage drop to prevent poor performance:

  • Lighting circuits: Maximum 3% (6.9V on 230V system)
  • Other circuits: Maximum 5% (11.5V on 230V system)

Voltage Drop Formula (Single Phase):

Vd = (mV/A/m × Length × Current) ÷ 1000

mV/A/m values are found in BS 7671 voltage drop tables (e.g., Table 4D5)

If voltage drop exceeds limits, increase cable size and recalculate.

Real-World Example: 9.5kW Electric Shower

Given: 9.5kW shower, 230V, 20m cable run, clipped direct, 30°C ambient

Step 1: Design current (Ib) = 9500W ÷ 230V = 41.3A

Step 2: Correction factors: Ca=1.0, Cg=1.0, Ci=1.0

Step 3: Required capacity: It = 41.3A ÷ 1.0 = 41.3A

Step 4: From Table 4D5, 6mm² twin & earth = 47A (clipped direct) ✓

Step 5: Voltage drop: (18 × 20 × 41.3) ÷ 1000 = 14.87V = 6.5%

⚠️ Voltage drop exceeds 5% limit!

Solution: Upgrade to 10mm² cable (voltage drop = 3.9%) ✓

Final answer: 10mm² twin & earth cable with 45A MCB

Important BS 7671 Cable Sizing Requirements

  • Cable must be able to carry the design current indefinitely (Regulation 512.1.5)
  • Protective device must disconnect before cable temperature becomes dangerous
  • Account for thermal insulation contact (Regulation 523.7)
  • Consider fault current and short circuit protection (Regulation 434.5.2)
  • All calculations must reference current BS 7671:2018+A2:2022 tables

💡 Pro Tip: Always use the calculator above for accurate results. Manual calculations are prone to errors, especially when multiple correction factors apply. The calculator automatically applies all BS 7671 requirements and checks voltage drop compliance.

Cable Size Chart UK - Quick Reference Guide

This cable size chart shows current ratings for common UK cable types. Values are for copper conductors at 30°C ambient with PVC insulation (70°C). Always verify with BS 7671 tables for your specific installation.

Twin & Earth Cable (6242Y) - Current Ratings

Cable SizeClipped DirectIn ConduitMax MCBTypical Use
1.0mm²15.5A13.5A10ALighting circuits
1.5mm²20A17.5A16ALighting, immersion heaters
2.5mm²27A24A20ARing mains, radial sockets
4.0mm²37A32A32ACooker circuits, high-power radials
6.0mm²47A41A40AElectric showers, small cookers
10.0mm²64A57A50ALarge cookers, EV chargers
16.0mm²85A76A63ASub-mains, large loads

Reference: BS 7671 Table 4D5 (Flat twin and earth cables, copper conductors, 70°C PVC)

SWA Cable (Steel Wire Armoured) - Current Ratings

Cable SizeClipped/TrayBuried DirectMax MCBTypical Use
2.5mm²28A35A25AGarden lighting, small outbuildings
4.0mm²37A45A32AGarages, workshops
6.0mm²47A57A40AEV chargers, hot tubs
10.0mm²64A78A50ALarger outbuildings, sub-mains
16.0mm²84A102A63ACommercial sub-mains
25.0mm²110A133A100AMain supplies, large installations

Reference: BS 7671 Table 4D4A (Armoured 70°C PVC cables, 2-core for single phase)

Common Cable Sizes for UK Installations

Here are typical cable sizes for common domestic and commercial installations. Always calculate for your specific cable length and installation method.

Electric Shower

7.5kW shower: 6mm² cable, 32A MCB

8.5kW shower: 6mm² cable, 40A MCB

9.5kW shower: 10mm² cable, 40A MCB

10.5kW+ shower: 10mm² cable, 45A MCB

Current = Power ÷ 230V (e.g., 9500W ÷ 230V = 41.3A)

Electric Cooker/Oven

Single oven (2-3kW): 2.5mm², 20A MCB

Double oven (5-6kW): 4mm², 32A MCB

Range cooker (8-10kW): 6mm², 40A MCB

Large range (12kW+): 10mm², 45A MCB

Note: Apply diversity for cookers with multiple rings

EV Charger

3.6kW (16A): 2.5mm² cable

7.4kW (32A): 6mm² cable (up to 20m)

7.4kW (32A): 10mm² cable (20-40m)

22kW (32A 3-phase): 6mm² 4-core SWA

Most home EV chargers are 7.4kW single phase

Immersion Heater

Standard (3kW): 2.5mm², 16A MCB

Long run (3kW, 20m+): 4mm², 16A MCB

Heat-resistant flex required at the heater connection

Ring Main (Sockets)

Standard ring: 2.5mm², 32A MCB

Floor area: Max 100m² per ring

Spurs: Max 1 per socket, same cable size

Radial circuits: 2.5mm²/20A (20m²) or 4mm²/32A (50m²)

Lighting Circuit

Domestic: 1.0mm² or 1.5mm², 6A MCB

Max per circuit: 12 lighting points

Voltage drop: Max 3% (6.9V)

Use 1.5mm² for longer runs or LED driver loads

Hot Tub / Spa

13A plug-in: Existing socket circuit

32A dedicated: 6mm² SWA

40A large spa: 10mm² SWA

RCD protection required - outdoor special location

Outbuilding / Garden Office

Light use: 4mm² SWA, 32A MCB

With heating: 6mm² SWA, 40A MCB

Workshop: 10mm² SWA, 63A MCB

SWA buried 450mm deep or in ducting

Air Conditioning Unit

Small split (1-2kW): 2.5mm², 16A MCB

Medium (3-5kW): 4mm², 20A MCB

Large (7kW+): 6mm², 32A MCB

Check manufacturer specs - motor starting current

Important: These are typical values only. Always calculate cable size for your specific installation considering cable length, installation method, ambient temperature, and grouping with other cables. Use the calculator above for accurate sizing.

Worked Examples - Step-by-Step Cable Size Calculations

Follow these detailed calculations for the most common UK electrical installations. All examples use BS 7671:2018+A2:2022 (18th Edition) standards.

1Cable Size for 7.4kW EV Charger (32A)

Scenario:

  • Load: 7.4kW single-phase EV charger
  • Cable run: 25 meters from consumer unit to garage
  • Installation: 6mm² SWA cable, buried direct 450mm deep
  • Voltage: 230V single-phase
  • Ambient: 20°C (buried underground)

Step 1 - Calculate Design Current:

Ib = 7400W ÷ 230V = 32.2A

Step 2 - Apply Correction Factors:

  • Installation method (buried direct): Ca = 1.0 (from Table 4D4A)
  • Ambient temp (20°C underground): Cg = 1.0
  • Grouping (single circuit): Ci = 1.0
  • Overall factor: 1.0 × 1.0 × 1.0 = 1.0

Step 3 - Required Capacity:

It = 32.2A ÷ 1.0 = 32.2A

Step 4 - Select Cable from BS 7671 Table 4D4A (SWA):

6mm² SWA buried direct = 57A rating ✓ (exceeds 32.2A)

Step 5 - Check Voltage Drop:

From Table 4D4A: 6mm² SWA = 7.3 mV/A/m

Vd = (7.3 × 25 × 32.2) ÷ 1000 = 5.88V

Percentage = (5.88 ÷ 230) × 100 = 2.56% ✓ (under 5% limit)

✓ Final Answer:

Use 6mm² 3-core SWA cable with 32A Type B MCB

Note: Ensure RCD protection (30mA) as per BS 7671 Regulation 722.531.2

2What Size Cable for 8.5kW Electric Shower?

Scenario:

  • Load: 8.5kW electric shower
  • Cable run: 12 meters from consumer unit
  • Installation: Twin & earth, clipped direct to wall
  • Voltage: 230V single-phase
  • Ambient: 30°C (standard)

Step 1 - Calculate Design Current:

Ib = 8500W ÷ 230V = 37A

Step 2 - Apply Correction Factors:

  • Installation method (clipped direct, Method C): Ca = 1.0
  • Ambient temp (30°C): Cg = 1.0
  • Grouping (single circuit): Ci = 1.0
  • Overall factor: 1.0

Step 3 - Required Capacity:

It = 37A ÷ 1.0 = 37A

Step 4 - Select Cable from BS 7671 Table 4D5:

6mm² twin & earth clipped direct = 47A ✓ (exceeds 37A)

Note: 4mm² = 37A would be borderline, use 6mm² for safety margin

Step 5 - Check Voltage Drop:

From Table 4D5: 6mm² = 7.3 mV/A/m

Vd = (7.3 × 12 × 37) ÷ 1000 = 3.24V

Percentage = (3.24 ÷ 230) × 100 = 1.41% ✓ (well under 5%)

✓ Final Answer:

Use 6mm² twin & earth cable with 40A Type B MCB

3Cable Size for 10kW Electric Cooker

Scenario:

  • Load: 10kW double oven + hob
  • Cable run: 8 meters from consumer unit
  • Installation: Twin & earth, clipped direct
  • Apply diversity (BS 7671 Appendix 15)

Step 1 - Calculate Design Current with Diversity:

Total load: 10kW = 43.5A at 230V

Apply cooker diversity:

  • First 10A at 100% = 10A
  • Remaining 33.5A at 30% = 10A
  • Plus 5A for socket outlet = 5A

Design current (Ib) = 10 + 10 + 5 = 25A

Step 2 - Required Capacity:

It = 25A ÷ 1.0 = 25A (no derating needed)

Step 3 - Select Cable:

4mm² twin & earth = 37A ✓ OR 6mm² = 47A for longer runs

Step 4 - Voltage Drop Check (using 6mm²):

Vd = (7.3 × 8 × 25) ÷ 1000 = 1.46V = 0.63% ✓

✓ Final Answer:

Use 6mm² twin & earth cable with 32A Type B MCB

Note: Diversity applied per BS 7671 Appendix 15 for cooking appliances

46mm Cable Amps - Current Rating Guide

The current rating of 6mm² cable depends on the installation method. Here are the ratings from BS 7671:

Installation MethodCurrent RatingMax MCBReference
Twin & Earth - Clipped Direct47A40ATable 4D5 Method C
Twin & Earth - In Conduit/Trunking41A32ATable 4D5 Method B
SWA - Clipped to Surface47A40ATable 4D4A Method C
SWA - Buried Direct57A50ATable 4D4A Method D

Important: These ratings assume 30°C ambient temperature and single circuit. Apply correction factors for grouped cables or high temperatures.

510mm Cable Rating - How Many Amps Can It Handle?

10mm² cable is commonly used for larger loads like big cookers, sub-mains, and high-power equipment:

Cable Type & MethodRating (Amps)Max MCBTypical Use
Twin & Earth - Clipped Direct64A50ALarge cookers, shower pumps
Twin & Earth - In Conduit57A50AProtected high-power circuits
SWA - Buried Direct78A63AOutbuilding sub-mains

Real-world example: A 40A shower (9.2kW) with 15m cable run would need 10mm² cable to keep voltage drop under 5%. Using 6mm² would result in 6.8% voltage drop (too high).

💡 Quick Cable Size Selection Tips

  • Always check voltage drop - this often determines cable size more than current rating
  • For long runs, increase cable size by one or two steps to reduce voltage drop
  • High-power loads (showers, cookers, EV chargers) typically need 6mm² or 10mm²
  • Use the calculator above for accurate results considering all BS 7671 requirements
  • When in doubt, go up a cable size - the cost difference is minimal compared to rewiring

How to Use the Cable Size Calculator

  1. Enter the load current - The maximum current (in Amps) that will flow through the cable. This can be calculated from the power rating of your equipment.
  2. Specify the cable length - The one-way distance (in meters) from your distribution board or consumer unit to the load.
  3. Select the voltage - Choose 230V for single-phase or 400V for three-phase installations.
  4. Choose the installation method - How the cable will be installed affects its current-carrying capacity due to different cooling conditions.
  5. Select conductor material - Copper is most common in UK installations. Aluminium has higher resistance but is lighter and cheaper for large cables.

Understanding the Results

  • Recommended Cable Size: The minimum cross-sectional area (in mm²) required for your installation
  • Voltage Drop: The voltage lost over the cable run as a percentage. Must be ≤5% for most circuits, ≤3% for lighting
  • Maximum Current: The current-carrying capacity of the selected cable with derating factors applied
  • Recommended MCB: The maximum circuit breaker rating suitable for the cable

BS 7671 Compliance Information

This calculator complies with BS 7671:2018+A2:2022 (18th Edition) - Requirements for Electrical Installations (IET Wiring Regulations).

Regulation 525 - Voltage Drop

Under normal service conditions, the voltage drop between the origin of the installation and the socket outlet or appliance shall not exceed:

  • 3% of the nominal voltage for lighting circuits
  • 5% of the nominal voltage for other circuits

Current-Carrying Capacity Considerations

The calculator applies derating factors for different installation methods as per Appendix 4 of BS 7671. Factors considered include:

  • Installation method (clipped direct, in conduit, etc.)
  • Ambient temperature (assumed 30°C)
  • Thermoplastic insulation (70°C rating)

Important: This calculator is a tool for initial sizing estimates. Final cable selection should be verified by a qualified electrician considering all installation-specific factors including grouping, thermal insulation, and harmonic currents.

Frequently Asked Questions