Cable Size Calculator - BS 7671 Compliant

Calculate the correct cable size for electrical installations according to British Standards BS 7671:2018+A2:2022

Calculate Cable Size

Enter your installation parameters to calculate the required cable size

Flat twin and earth cable with PVC insulationDomestic fixed wiring - lighting, sockets, cookers

Amps

The maximum current the circuit will carry

meters

One-way cable run distance from distribution board to load

How the cable will be installed (affects current carrying capacity)

What Size Cable Do I Need? Quick Answer

Cable size in the UK depends on the circuit's design current, installation method, and cable run length per BS 7671:2018+A2:2022. For domestic installations: use 1.0mm² or 1.5mm² for lighting circuits (6A-10A MCB), 2.5mm² for socket ring mains (32A MCB), 6.0mm² for electric showers up to 9.5kW, and 10.0mm² for showers above 9.5kW or long cable runs where voltage drop exceeds the 5% limit. All cable sizes must be verified against BS 7671 current-carrying capacity tables with correction factors applied.

kW to Cable Size Conversion (Single Phase, 230V)

To convert kW to cable size, divide the power in watts by 230V to find the design current in amps, then select the cable from BS 7671 tables. This table shows typical cable sizes for common load ratings at 230V single phase, assuming clipped direct installation at 30°C ambient with no grouping.

Load (kW)Current (A)Cable SizeMCB RatingTypical Application
1-2 kW4.3-8.7A1.0-1.5mm²6-10ALighting circuits
3 kW13.0A2.5mm²16AImmersion heater, small appliances
5-6 kW21.7-26.1A4.0mm²32ASmall cooker, hob
7-8.5 kW30.4-37.0A6.0mm²40AElectric shower, EV charger (7kW)
9.5-10 kW41.3-43.5A10.0mm²45-50ALarge shower, cooker, EV charger (10kW)
12-15 kW52.2-65.2A16.0mm²63ASub-main to outbuilding, 3-phase loads

Cable sizes assume short cable runs (<15m) with no grouping or thermal insulation derating. For longer runs, voltage drop may require upsizing — use the calculator above to check. Reference: BS 7671 Table 4D5 (twin & earth copper conductors, 70°C PVC insulation).

How to Calculate Cable Size UK - Complete Guide

Calculating the correct cable size for UK electrical installations requires consideration of several critical factors according to BS 7671 wiring regulations. This guide explains the complete process step-by-step.

Step 1: Determine the Design Current (Ib)

The design current is the maximum current your circuit will carry under normal operating conditions.

  • For known loads: Divide the power (watts) by voltage. Example: 9.5kW shower ÷ 230V = 41.3A
  • For socket circuits: Use the circuit breaker rating (e.g., 32A for ring main)
  • For motors: Check the motor nameplate for full load current

Step 2: Apply Correction Factors

BS 7671 requires cable sizing to account for installation conditions that affect heat dissipation:

Installation Method (Ca)

  • Clipped direct (Method C): Factor = 1.0 (best cooling)
  • In conduit on walls (Method B): Factor = 0.95
  • In thermal insulation (Method A): Factor = 0.5-0.89 (worst cooling)

Ambient Temperature (Cg)

Standard is 30°C. For loft spaces (45°C) or other hot environments, apply temperature correction from BS 7671 Table 4B1.

Grouped Circuits (Ci)

Multiple cables grouped together generate more heat. Correction factors from BS 7671 Table 4C1.

Step 3: Calculate Required Current Carrying Capacity (It)

Divide your design current by the overall correction factor:

It = Ib ÷ (Ca × Cg × Ci)

Example: 32A circuit, in conduit (0.95), at 30°C (1.0), with 2 cables (0.8):
It = 32A ÷ (0.95 × 1.0 × 0.8) = 42.1A required capacity

Step 4: Select Cable Size from BS 7671 Tables

Choose the cable size from the appropriate BS 7671 table based on your cable type and installation method:

  • Table 4D5: Twin and earth cables (most common domestic)
  • Table 4D4A: Steel wire armoured (SWA) cables
  • Table 4E4A: Single-core cables in conduit

Select the smallest cable size that has a current rating ≥ It (your calculated capacity)

Step 5: Check Voltage Drop

BS 7671 Regulation 525 limits voltage drop to prevent poor performance:

  • Lighting circuits: Maximum 3% (6.9V on 230V system)
  • Other circuits: Maximum 5% (11.5V on 230V system)

Voltage Drop Formula (Single Phase):

Vd = (mV/A/m × Length × Current) ÷ 1000

mV/A/m values are found in BS 7671 voltage drop tables (e.g., Table 4D5)

If voltage drop exceeds limits, increase cable size and recalculate.

Real-World Example: 9.5kW Electric Shower

Given: 9.5kW shower, 230V, 20m cable run, clipped direct, 30°C ambient

Step 1: Design current (Ib) = 9500W ÷ 230V = 41.3A

Step 2: Correction factors: Ca=1.0, Cg=1.0, Ci=1.0

Step 3: Required capacity: It = 41.3A ÷ 1.0 = 41.3A

Step 4: From Table 4D5, 6mm² twin & earth = 47A (clipped direct) ✓

Step 5: Voltage drop: (18 × 20 × 41.3) ÷ 1000 = 14.87V = 6.5%

⚠️ Voltage drop exceeds 5% limit!

Solution: Upgrade to 10mm² cable (voltage drop = 3.9%) ✓

Final answer: 10mm² twin & earth cable with 45A MCB

Important BS 7671 Cable Sizing Requirements

  • Cable must be able to carry the design current indefinitely (Regulation 512.1.5)
  • Protective device must disconnect before cable temperature becomes dangerous
  • Account for thermal insulation contact (Regulation 523.7)
  • Consider fault current and short circuit protection (Regulation 434.5.2)
  • All calculations must reference current BS 7671:2018+A2:2022 tables

💡 Pro Tip: Always use the calculator above for accurate results. Manual calculations are prone to errors, especially when multiple correction factors apply. The calculator automatically applies all BS 7671 requirements and checks voltage drop compliance. For full BS 7671 cable current rating tables and correction factor reference data, see the SparkyHub cable ratings guide.

The Cable Sizing Hierarchy: Ib ≤ In ≤ Iz

BS 7671 Regulation 433.1.1 expresses cable sizing as a coordination inequality. Every correctly sized UK circuit satisfies three currents in ascending order — memorising this framework is how electricians verify a cable choice in one pass.

Ib ≤ In ≤ Iz

Ib — Design Current

The current the circuit is designed to carry in normal service. Calculated from load power (W ÷ V) or taken from the protective device rating after diversity.

In — Nominal Protective Device Rating

The rated current of the MCB, RCBO or fuse protecting the circuit (BS EN 60898, BS EN 61009, BS 88, BS 3036). Must equal or exceed Ib.

Iz — Cable Current-Carrying Capacity

The tabulated cable rating It (Appendix 4, Tables 4D1–4J4) after all correction factors: Iz = It × Ca × Cg × Ci × Cc.

The Four Correction Factors (Ca, Cg, Ci, Cc)

FactorAccounts ForBS 7671 ReferenceTypical Range
CaAmbient temperature (if not 30°C)Table 4B10.71–1.22
CgGrouping of circuits on the same surface or enclosureTable 4C1–4C50.40–1.00
CiThermal insulation (cable buried in insulation)Reg 523.9, Table 4A20.50–0.89
CcType of protective device (0.725 for BS 3036 rewirable fuses)Reg 433.1.10.725–1.00

For modern MCBs (BS EN 60898) and RCBOs (BS EN 61009), Cc = 1.0 and can be omitted. It only applies to semi-enclosed rewirable fuses still found in some legacy domestic consumer units.

Worked Example: Verifying the Hierarchy

Circuit: 32A ring final, 2.5mm² T&E, in plasterboard ceiling with >100mm insulation on one side

Ib: 32A (design current)

In: 32A Type B MCB (BS EN 60898) → Ib ≤ In

It: 27A (Table 4D5, Method C clipped direct)

Corrections: Ca=1.0 (30°C), Cg=1.0 (not grouped), Ci=0.75 (Method 101), Cc=1.0 (MCB)

Iz: 27 × 0.75 = 20.25A

✗ In (32A) > Iz (20.25A) — FAILS the hierarchy. Cable must be upsized to 4.0mm² (It=37A, Iz=27.75A ≥ 32A ✓).

Pro tip: the calculator above runs the full hierarchy check automatically. Use this framework when reviewing manual designs or inspecting existing installations to spot under-sized cables fast.

Cable Size Chart UK - Quick Reference Guide

This cable size chart shows current ratings for common UK cable types. Values are for copper conductors at 30°C ambient with PVC insulation (70°C). Always verify with BS 7671 tables for your specific installation.

Twin & Earth Cable (6242Y) - Current Ratings

Cable SizeClipped DirectIn ConduitMax MCBTypical Use
1.0mm²15.5A13.5A10ALighting circuits
1.5mm²20A17.5A16ALighting, immersion heaters
2.5mm²27A24A20ARing mains, radial sockets
4.0mm²37A32A32ACooker circuits, high-power radials
6.0mm²47A41A40AElectric showers, small cookers
10.0mm²64A57A50ALarge cookers, EV chargers
16.0mm²85A76A63ASub-mains, large loads

Reference: BS 7671 Table 4D5 (Flat twin and earth cables, copper conductors, 70°C PVC)

SWA Cable (Steel Wire Armoured) - Current Ratings

Cable SizeClipped/TrayBuried DirectMax MCBTypical Use
2.5mm²28A35A25AGarden lighting, small outbuildings
4.0mm²37A45A32AGarages, workshops
6.0mm²47A57A40AEV chargers, hot tubs
10.0mm²64A78A50ALarger outbuildings, sub-mains
16.0mm²84A102A63ACommercial sub-mains
25.0mm²110A133A100AMain supplies, large installations

Reference: BS 7671 Table 4D4A (Armoured 70°C PVC cables, 2-core for single phase)

Fire-Rated, Mineral-Insulated and Flexible Cables — UK Sizing Reference

BS 7671 cable sizing tables cover more than twin & earth and SWA. Commercial installations, fire alarm systems, escape-route lighting and machinery wiring all use cables that electricians must size correctly under BS 5839-1, BS 5266-1 and BS EN 60204-1.

Fire-Rated Cables (FP200, FP400, Firetuf, Prysmian FP PLUS)

Fire-resistant cables maintain circuit integrity during a fire — essential for fire alarms (BS 5839-1), emergency lighting (BS 5266-1), smoke control systems and sprinkler pumps. Ratings are specified by BS 8491 / BS EN 50200 survival times (PH30, PH60, PH120) and the "Enhanced" category (BS 8434-2).

Cable SizeClipped Direct (A)In Conduit (A)Typical Use
1.0mm²15A11.5AFire alarm detector loops, interface units
1.5mm²19.5A15AEmergency lighting circuits (230V)
2.5mm²27A20ASounder circuits, powered escape signs
4.0mm²36A27ASmoke extract fans, sprinkler pumps (small)
6.0mm²46A34AFire pump sub-mains, stair pressurisation

Typical values — always verify against manufacturer data sheet. Standard FP-range cables meet PH30/PH60 per BS EN 50200; use "Enhanced" grade (BS 8434-2) where specified by the fire strategy (e.g. high-rise residential common areas).

Mineral-Insulated Copper Cable (MICC / Pyro) — BS 7671 Table 4H1A–4H4A

MICC (branded Pyrotenax, Wrexham MIMS) uses compacted magnesium-oxide insulation in a copper sheath — it is non-combustible, withstands temperatures up to 250°C in service and passes BS 6387 CWZ. Used on fire alarms in heritage buildings, process plant and where the highest fire-survival rating is specified.

Conductor Size500V MICC (A)750V MICC (A)Reference
1.0mm²20A21ATable 4H1A
1.5mm²25A26ATable 4H1A
2.5mm²34A35ATable 4H1A
4.0mm²45A46ATable 4H1A
10.0mm²84A86ATable 4H1A

Values for bare MICC, single-core, exposed to touch. Sheathed (LSF overall) cable uses lower ratings — see Table 4H2A. MICC has extremely low voltage drop (higher conductor operating temperature raises resistance only modestly).

Flexible Cables — SY, H07RN-F, 3183Y, 3184Y

Flexibles are used for machinery connections (BS EN 60204-1), generators, temporary power, festoon lighting and appliance leads. Sizing uses Table 4F3A (light PVC flex) and Table 4H3A (heavy-duty rubber flex).

Cable TypeJacketTypical Application1.5mm² / 2.5mm² Rating
3183Y / 3184YPVCAppliance leads, pendant luminaires16A / 25A
H05VV-FPVC (harmonised)Class II appliance flex, indoor use16A / 25A
H07RN-FRubber (EPR)Generator leads, site power, outdoor use, mobile machinery20A / 27A
SY (CY/YY)PVC + braided screenMachinery control, inverter/VSD motor cables16A / 21A
Arctic grade (3183A)PVC (-25°C cold flex)110V site extension leads, cold-store cabling16A / 25A

Note: SY cables are not armoured in the BS 7671 sense — the braid is a mechanical screen, not a BS EN 60228 Class 4 earth. Do not rely on the screen as a CPC. BS 7629 "braided screen" cables are equivalent.

LSZH / LSF Insulation — What's the Difference?

LSZH (Low Smoke Zero Halogen) meets IEC 60754-1/-2 — emits no corrosive halogen gases if burned. Used on London Underground, hospitals, data centres, high-rise escape routes (Approved Document B). LSF (Low Smoke & Fumes) is a lower-specification modified PVC — still contains halogens but reduces smoke density. For current-carrying capacity both are treated as 70°C thermoplastic insulation (Tables 4D/4E), so the BS 7671 ratings are identical to standard PVC.

Common Cable Sizes for UK Installations

Here are typical cable sizes for common domestic and commercial installations. Always calculate for your specific cable length and installation method.

Electric Shower

7.5kW shower: 6mm² cable, 32A MCB

8.5kW shower: 6mm² cable, 40A MCB

9.5kW shower: 10mm² cable, 40A MCB

10.5kW+ shower: 10mm² cable, 45A MCB

Current = Power ÷ 230V (e.g., 9500W ÷ 230V = 41.3A)

Electric Cooker/Oven

Single oven (2-3kW): 2.5mm², 20A MCB

Double oven (5-6kW): 4mm², 32A MCB

Range cooker (8-10kW): 6mm², 40A MCB

Large range (12kW+): 10mm², 45A MCB

Note: Apply diversity for cookers with multiple rings

EV Charger

3.6kW (16A): 2.5mm² cable

7.4kW (32A): 6mm² cable (up to 20m)

7.4kW (32A): 10mm² cable (20-40m)

22kW (32A 3-phase): 6mm² 4-core SWA

Most home EV chargers are 7.4kW single phase

Immersion Heater

Standard (3kW): 2.5mm², 16A MCB

Long run (3kW, 20m+): 4mm², 16A MCB

Heat-resistant flex required at the heater connection

Ring Main (Sockets)

Standard ring: 2.5mm², 32A MCB

Floor area: Max 100m² per ring

Spurs: Max 1 per socket, same cable size

Radial circuits: 2.5mm²/20A (20m²) or 4mm²/32A (50m²)

Lighting Circuit

Domestic: 1.0mm² or 1.5mm², 6A MCB

Max per circuit: 12 lighting points

Voltage drop: Max 3% (6.9V)

Use 1.5mm² for longer runs or LED driver loads

Hot Tub / Spa

13A plug-in: Existing socket circuit

32A dedicated: 6mm² SWA

40A large spa: 10mm² SWA

RCD protection required - outdoor special location

Outbuilding / Garden Office

Light use: 4mm² SWA, 32A MCB

With heating: 6mm² SWA, 40A MCB

Workshop: 10mm² SWA, 63A MCB

SWA buried 450mm deep or in ducting

Air Conditioning Unit

Small split (1-2kW): 2.5mm², 16A MCB

Medium (3-5kW): 4mm², 20A MCB

Large (7kW+): 6mm², 32A MCB

Check manufacturer specs - motor starting current

Important: These are typical values only. Always calculate cable size for your specific installation considering cable length, installation method, ambient temperature, and grouping with other cables. Use the calculator above for accurate sizing.

Worked Examples - Step-by-Step Cable Size Calculations

Follow these detailed calculations for the most common UK electrical installations. All examples use BS 7671:2018+A2:2022 (18th Edition) standards.

1Cable Size for 7.4kW EV Charger (32A)

Scenario:

  • Load: 7.4kW single-phase EV charger
  • Cable run: 25 meters from consumer unit to garage
  • Installation: 6mm² SWA cable, buried direct 450mm deep
  • Voltage: 230V single-phase
  • Ambient: 20°C (buried underground)

Step 1 - Calculate Design Current:

Ib = 7400W ÷ 230V = 32.2A

Step 2 - Apply Correction Factors:

  • Installation method (buried direct): Ca = 1.0 (from Table 4D4A)
  • Ambient temp (20°C underground): Cg = 1.0
  • Grouping (single circuit): Ci = 1.0
  • Overall factor: 1.0 × 1.0 × 1.0 = 1.0

Step 3 - Required Capacity:

It = 32.2A ÷ 1.0 = 32.2A

Step 4 - Select Cable from BS 7671 Table 4D4A (SWA):

6mm² SWA buried direct = 57A rating ✓ (exceeds 32.2A)

Step 5 - Check Voltage Drop:

From Table 4D4A: 6mm² SWA = 7.3 mV/A/m

Vd = (7.3 × 25 × 32.2) ÷ 1000 = 5.88V

Percentage = (5.88 ÷ 230) × 100 = 2.56% ✓ (under 5% limit)

✓ Final Answer:

Use 6mm² 3-core SWA cable with 32A Type B MCB

Note: Ensure RCD protection (30mA) as per BS 7671 Regulation 722.531.2

2What Size Cable for 8.5kW Electric Shower?

Scenario:

  • Load: 8.5kW electric shower
  • Cable run: 12 meters from consumer unit
  • Installation: Twin & earth, clipped direct to wall
  • Voltage: 230V single-phase
  • Ambient: 30°C (standard)

Step 1 - Calculate Design Current:

Ib = 8500W ÷ 230V = 37A

Step 2 - Apply Correction Factors:

  • Installation method (clipped direct, Method C): Ca = 1.0
  • Ambient temp (30°C): Cg = 1.0
  • Grouping (single circuit): Ci = 1.0
  • Overall factor: 1.0

Step 3 - Required Capacity:

It = 37A ÷ 1.0 = 37A

Step 4 - Select Cable from BS 7671 Table 4D5:

6mm² twin & earth clipped direct = 47A ✓ (exceeds 37A)

Note: 4mm² = 37A would be borderline, use 6mm² for safety margin

Step 5 - Check Voltage Drop:

From Table 4D5: 6mm² = 7.3 mV/A/m

Vd = (7.3 × 12 × 37) ÷ 1000 = 3.24V

Percentage = (3.24 ÷ 230) × 100 = 1.41% ✓ (well under 5%)

✓ Final Answer:

Use 6mm² twin & earth cable with 40A Type B MCB

3Cable Size for 10kW Electric Cooker

Scenario:

  • Load: 10kW double oven + hob
  • Cable run: 8 meters from consumer unit
  • Installation: Twin & earth, clipped direct
  • Apply diversity (BS 7671 Appendix 15)

Step 1 - Calculate Design Current with Diversity:

Total load: 10kW = 43.5A at 230V

Apply cooker diversity:

  • First 10A at 100% = 10A
  • Remaining 33.5A at 30% = 10A
  • Plus 5A for socket outlet = 5A

Design current (Ib) = 10 + 10 + 5 = 25A

Step 2 - Required Capacity:

It = 25A ÷ 1.0 = 25A (no derating needed)

Step 3 - Select Cable:

4mm² twin & earth = 37A ✓ OR 6mm² = 47A for longer runs

Step 4 - Voltage Drop Check (using 6mm²):

Vd = (7.3 × 8 × 25) ÷ 1000 = 1.46V = 0.63% ✓

✓ Final Answer:

Use 6mm² twin & earth cable with 32A Type B MCB

Note: Diversity applied per BS 7671 Appendix 15 for cooking appliances

46mm Cable Amps - Current Rating Guide

The current rating of 6mm² cable depends on the installation method. Here are the ratings from BS 7671:

Installation MethodCurrent RatingMax MCBReference
Twin & Earth - Clipped Direct47A40ATable 4D5 Method C
Twin & Earth - In Conduit/Trunking41A32ATable 4D5 Method B
SWA - Clipped to Surface47A40ATable 4D4A Method C
SWA - Buried Direct57A50ATable 4D4A Method D

Important: These ratings assume 30°C ambient temperature and single circuit. Apply correction factors for grouped cables or high temperatures.

510mm Cable Rating - How Many Amps Can It Handle?

10mm² cable is commonly used for larger loads like big cookers, sub-mains, and high-power equipment:

Cable Type & MethodRating (Amps)Max MCBTypical Use
Twin & Earth - Clipped Direct64A50ALarge cookers, shower pumps
Twin & Earth - In Conduit57A50AProtected high-power circuits
SWA - Buried Direct78A63AOutbuilding sub-mains

Real-world example: A 40A shower (9.2kW) with 15m cable run would need 10mm² cable to keep voltage drop under 5%. Using 6mm² would result in 6.8% voltage drop (too high).

💡 Quick Cable Size Selection Tips

  • Always check voltage drop - this often determines cable size more than current rating
  • For long runs, increase cable size by one or two steps to reduce voltage drop
  • High-power loads (showers, cookers, EV chargers) typically need 6mm² or 10mm²
  • Use the calculator above for accurate results considering all BS 7671 requirements
  • When in doubt, go up a cable size - the cost difference is minimal compared to rewiring

3-Phase Cable Size Calculator — BS 7671 Worked Examples

Three-phase cable sizing follows the same BS 7671 hierarchy as single-phase but uses 400V line-to-line (230V line-to-neutral), the √3 factor when converting between kW and line current, and Table 4D4A columns for 3- or 4-core cables. For the full industrial 3-phase treatment — motor full-load currents, star/delta starting, harmonic neutral sizing, and 4-core SWA derating — see the dedicated 3-Phase Cable Size Calculator.

Three-Phase Current and Voltage Drop Formulas

Line Current (balanced load):

IL = P ÷ (√3 × VLL × PF)

Where VLL = 400V, PF = power factor (1.0 for resistive loads, 0.8 typical for motors)

3-Phase Voltage Drop:

Vd = (mV/A/m × L × IL × √3) ÷ 1000

Use the 3-phase mV/A/m column in Table 4D4B / 4E4B (typically ~87% of single-phase value for the same cable)

122kW Three-Phase EV Charger (32A per phase)

Scenario:

  • Load: 22kW three-phase EV charger, balanced across L1/L2/L3
  • Cable: 4-core SWA, buried direct 600mm
  • Run length: 45m from sub-main to garage
  • Voltage: 400V line-to-line, PF = 1.0 (modern PFC-corrected charger)

Step 1 — Line current:

IL = 22000 ÷ (√3 × 400 × 1.0) = 22000 ÷ 692.8 = 31.8A per phase

Step 2 — Select protective device:

32A Type B 3-pole MCB (BS EN 60898) — In = 32A ≥ Ib

Step 3 — Current-carrying capacity check (Table 4D4A, 4-core SWA, Method D buried direct):

6mm² = 38A (column 7); Iz = 38 × 1.0 × 1.0 × 1.0 = 38A ≥ 31.8A ✓

Step 4 — Voltage drop (3-phase, Table 4D4B):

6mm² 4-core SWA 3-phase mV/A/m = 6.4

Vd = (6.4 × 45 × 31.8 × √3) ÷ 1000 = 15.88V

As % of 400V line-to-line = 3.97% ✓ (under 5%)

✓ Final answer:

Use 6mm² 4-core SWA with 32A Type B 3-pole MCBand 30mA Type B RCD (BS 7671 Section 722 — EV-specific RCD requirement).

Note: a single-phase 32A 7.4kW charger on the same 45m run would need 10mm² SWA (Vd = 4.3% at 6mm², 2.6% at 10mm²). Three-phase halves the cable size because each phase only carries a third of the total power.

2100A Three-Phase Sub-Main to Workshop

Scenario:

  • Load: 100A TP&N sub-main feeding workshop distribution board
  • Cable: 4-core SWA, clipped to tray
  • Run length: 35m, budget ≤ 2% voltage drop (leaving 3% for final circuits)

Step 1 — Capacity: Ib = 100A, In = 100A (BS 88-3 fuse or moulded-case CB)

Step 2 — First-pass cable (Table 4D4A, Method E clipped to tray, column 5):

25mm² 4-core SWA = 110A ✓; 16mm² = 83A ✗ (insufficient)

Step 3 — Voltage drop at 25mm² (Table 4D4B, 3-phase z column):

25mm² 3-phase mV/A/m = 1.50

Vd = (1.50 × 35 × 100 × √3) ÷ 1000 = 9.09V

As % of 400V = 2.27% — over 2% budget

Step 4 — Upsize to 35mm²:

mV/A/m = 1.10; Vd = (1.10 × 35 × 100 × √3) ÷ 1000 = 6.67V = 1.67%

✓ Final answer:

Use 35mm² 4-core SWA with 100A BS 88-3 fuse (or MCCB). Armour continuity checked against adiabatic equation for CPC duty; add 16mm² external earth if Zs calc demands it.

kW → 3-Phase Current Quick Reference (400V, balanced, PF=1.0)

Load (kW)Line current (A)Typical MCBTypical cable (≤30m)
11 kW15.9A16A / 20A TP2.5mm² 4-core SWA
22 kW31.8A32A TP6mm² 4-core SWA
30 kW43.3A50A TP10mm² 4-core SWA
45 kW65A80A TP fuse16mm² 4-core SWA
69 kW100A100A BS 88-325–35mm² 4-core SWA

For PF < 1.0 (typical 0.85 for motor-heavy loads), scale up the current by 1/PF. Example: 22kW motor at 0.85 PF → 37.4A per phase, step up to 10mm² SWA.

Critical Cable Sizing Mistakes UK Electricians Must Avoid

These common errors can result in failed inspections, dangerous installations, or expensive rewiring. Understanding these traps is essential for BS 7671 compliance.

1The Thermal Insulation Trap (Reference Methods 100-103)

Modern homes with 270mm+ loft insulation create a critical derating scenario that many electricians miss. When cables are buried in thermal insulation, heat cannot dissipate.

Reference MethodScenarioDerating Factor (Ci)
Method 100Clipped to joist, <100mm insulation0.89
Method 101Clipped to joist, >100mm insulation0.5
Method 102In stud wall, not touching inner wall0.89
Method 103In stud wall, touching inner wall0.5

Real Impact: A 2.5mm² cable rated at 27A clipped direct becomes just 13.5Aunder Method 101. This is insufficient for a 32A ring circuit. The circuit requires upsizing to 4mm² or 6mm².

Reference: BS 7671 Regulation 523.9 and Table 4A2 (Amendment 3)

2The 1.45 Rule and Rewirable Fuses (BS 3036)

BS 7671 Regulation 433.1.1 requires that the current causing effective operation of the protective device (I₂) must not exceed 1.45 times the cable's current-carrying capacity (Iz).

I₂ ≤ 1.45 × Iz

For modern MCBs (BS EN 60898), this is automatically satisfied because I₂ = 1.45 × In. However, for BS 3036 rewirable fuses, the fusing factor is approximately 2.0.

Critical: When using rewirable fuses, you must apply an additional derating factor of 0.725 to the cable capacity. A 27A cable becomes effectively 19.6A.

Many older domestic consumer units still use rewirable fuses. Always check before sizing cables.

390°C Cable vs 70°C Terminals

SWA cables with XLPE insulation are rated for 90°C operation and have higher current ratings than 70°C PVC cables. However, this creates a hidden problem.

The Problem: Most domestic consumer units, MCBs, and terminal blocks are rated for70°C maximum. Running an XLPE cable at 90°C will conduct excessive heat into the terminals, causing nuisance tripping or terminal damage.

Solution: When using XLPE/SWA cables with standard 70°C terminals, use the 70°C current ratings from BS 7671 tables, not the 90°C ratings. The benefit of XLPE is only realised when both the cable AND terminals are rated for 90°C.

4Ignoring Cumulative Voltage Drop

Voltage drop is cumulative through an installation. Many electricians calculate the final circuit drop but forget the sub-main contribution.

Total Voltage Drop = Sub-main + Final Circuit

Example: 1.5% (sub-main) + 4% (final circuit) = 5.5% (FAIL)

Best Practice: Budget your 5% allowance carefully:

  • Sub-mains: Allow maximum 1.5-2%
  • Final circuits: Allow maximum 3-3.5%
  • Total: Keep under 5% with margin

5The Physical Reality Problem

Calculations may suggest a cable size that is electrically correct but physically impossible.

Example: High derating factors on a 32A ring circuit might suggest 10mm² cable. However, 10mm² cable will not fit into the terminals of a standard 13A double socket. Maximum terminal capacity is typically 2.5mm² or 4mm².

Solutions:

  • Use junction boxes with larger terminals for cable transitions
  • Consider radial circuits instead of rings for heavily derated installations
  • Route cables to avoid severe derating conditions

Key Takeaway

Cable sizing is not just about current capacity. It requires simultaneous verification of thermal conditions, voltage drop, protective device coordination, physical terminations, and earth fault loop impedance. Use this calculator and always verify calculations against your specific installation conditions.

UK Trade Practice vs BS 7671 Minimum — When Sparkies Always Upsize

BS 7671 gives the minimum legally-compliant cable size. On real jobs, UK electricians habitually upsize beyond the minimum for four reasons: voltage-drop headroom on future loads, margin for installation errors, ease of future diversity changes, and avoiding call-backs. These are the canonical "trade rules" that every experienced sparky applies.

1. 8kW+ Electric Showers → 10mm² (even when 6mm² calculates)

BS 7671 minimum for an 8.5kW shower on a short run is 6mm² T&E. Trade practice installs 10mm² on anything 8kW or above. Reasons: homeowners often upgrade to a 9.5kW or 10.5kW unit later, power-shower boost pumps add load, and the extra cost (~£2/m) is less than the cost of returning to re-pull cable.

This is the most widely-cited unwritten rule in UK domestic wiring — referenced in JIB, NICEIC and Elecsa guidance alike.

2. EV Chargers → default 10mm² for home wallbox (OZEV / future 11kW upgrade)

A 7.4kW 32A wallbox on a 15m clipped run calculates as 6mm² SWA. Trade practice pulls 10mm² because (a) householders commonly upgrade to a second phase or 11kW charger within 5 years, (b) 10mm² keeps voltage drop under 3% for PEN-protection algorithms (BS 7671 722.411.4.1 iii), and (c) grant-funded OZEV installations are often inspected against conservative interpretations.

3. Garage / Outbuilding Sub-Main → 10mm² SWA minimum

A 32A outbuilding with 2kW of lighting and a few sockets calculates as 6mm² SWA. Trade practice goes to 10mm² because workshops gain heating, compressors, welders and EV chargers over time. 10mm² also gives headroom for the armour to serve as the sole CPC under the adiabatic equation when Zs is high.

4. Lighting Circuits > 8 metres → 1.5mm² (not 1.0mm²)

BS 7671 permits 1.0mm² T&E on a 6A lighting circuit up to ~45m for voltage drop. Trade practice defaults to 1.5mm² on any new-build rewire because (a) future LED → incandescent retrofits are rare but inrush on LED driver banks can be substantial, (b) 1.5mm² handles 10A if a circuit is later split, and (c) the unit-price difference is under £5 on a typical property.

5. Ring Final in a Kitchen → 4mm² radial preferred over 2.5mm² ring

Modern kitchens with induction hob, oven, microwave, kettle and dishwasher can approach 32A on a single appliance bank. Many installers now prefer a 4mm² radial on a 32A MCB (or two 2.5mm² radials on 20A MCBs) over the traditional ring final — better voltage stability under simultaneous load, easier fault finding and less copper than a large ring.

6. Submain into a Consumer Unit → 16mm² tails even when 10mm² suffices

DNO 80A/100A cutouts feed consumer unit tails. BS 7671 allows 16mm² 6181Y meter tails up to 80A and 25mm² for 100A. Trade practice (and many DNOs) specifies 25mm² tails on every new installation regardless of maximum demand, because the tails are rarely replaced when the DNO upgrades the cutout from 80A to 100A years later.

Why this matters: a calculator can only tell you the minimum BS 7671-compliant cable. The best UK electricians treat the calculator as a floor, not a target — and build in headroom for the next 10 years of load growth. If a homeowner adds an EV, hot tub, or heat pump and the rewire was sized exactly to today's load, the upgrade becomes a full re-pull rather than a consumer-unit swap.

Advanced Cable Sizing Considerations - BS 7671

For commercial, industrial, and complex residential installations, these advanced factors must be considered beyond basic current and voltage drop calculations.

Harmonic Currents and Neutral Sizing

Modern LED lighting, IT equipment, and Variable Speed Drives (VSDs) are non-linear loads that create harmonic currents. The third harmonic (150Hz) is particularly problematic in three-phase systems.

The Physics: Third harmonic currents from all three phases are in-phase (0° apart instead of 120°). They don't cancel at the neutral point—they add together.

3rd Harmonic ContentPhase Reduction FactorNeutral Sizing
0-15%1.0Standard (same as phase)
15-33%0.86Standard (same as phase)
33-45%0.86Neutral = Phase size
>45%By calculationNeutral may exceed phase

Reference: BS 7671 Regulation 523.6.3 and Appendix 4, Section 11

The 30% Grouping Rule - Reduce Cable Sizes Legitimately

BS 7671 contains an often-overlooked provision that can significantly reduce cable costs on commercial installations.

The Rule: Cables carrying no more than 30% of their grouped ratingmay be excluded from grouping factor calculations.

Practical Application:

  • If 6 cables are grouped but 2 are lighting circuits running at only 2A (10% of capacity), these can be excluded from grouping
  • This effectively reduces the group from 6 circuits (Cg=0.57) to 4 circuits (Cg=0.65)
  • The remaining 4 cables can be smaller, saving significant material costs

Reference: BS 7671 Table 4C1, Note 3

Motor Circuits - Inrush Current Considerations

Induction motors draw 6-8 times their Full Load Current (FLC) during Direct-On-Line (DOL) starting. While cable current capacity is sized for running current, voltage drop during starting can cause problems.

Starting Voltage Drop: A cable sized for 5% voltage drop at running current will experience 30-40% drop during starting (6-8× current). If this exceeds 15%, the motor may stall or the contactor may chatter.

Sizing Approach for Motors:

  • Size current capacity for running FLC
  • Check voltage drop at starting current (not running)
  • Ensure starting drop does not exceed 15% for sensitive motors
  • Consider soft starters or VFDs for long cable runs

Adiabatic Equation - CPC Sizing for Fault Protection

The Circuit Protective Conductor (CPC/Earth) must withstand the thermal stress of a fault without damage. BS 7671 Regulation 543.1.3 provides the adiabatic equation:

S = √(I²t) / k

Variables:

  • S = Minimum CPC size (mm²)
  • I = Fault current (A)
  • t = Disconnection time (s)
  • k = Material factor

k values:

  • Copper/PVC: 115
  • Copper/XLPE: 143
  • Steel armour: 51

SWA Cable Note: The steel armour of SWA cables often serves as the CPC. Due to the lower k factor (51 vs 115), the armour may be insufficient for high fault currents. Always verify with the adiabatic equation and add external earth cable if needed.

Earth Fault Loop Impedance (Zs) and Cable Selection

Cable selection must ensure the earth fault loop impedance (Zs) is low enough to guarantee protective device operation within required disconnection times.

Zs = Ze + (R1 + R2) × L × Cr / 1000

Ze = External earth fault loop impedance

TN-C-S (PME): 0.35Ω typical

TN-S: 0.8Ω typical

R1+R2 = Resistance per metre (mΩ/m)

L = Cable length (m)

Cr = Temperature correction (1.2 for 70°C)

Practical Impact: Type C MCBs require much lower Zs than Type B for the same rating. This often dictates using larger cables or shorter runs with Type C devices.

MCB RatingType B Max ZsType C Max Zs
16A2.73Ω1.37Ω
32A1.37Ω0.68Ω
63A0.70Ω0.35Ω

Professional Resources

For complex installations, always reference:

  • BS 7671:2018+A2:2022 Appendix 4 - Current-carrying capacities and voltage drop
  • IET Guidance Note 1 - Selection and Erection of Equipment
  • IET On-Site Guide - Quick reference for inspection and testing
  • Manufacturer cable data sheets for specific XLPE/SWA properties

How to Use the Cable Size Calculator

  1. Enter the load current - The maximum current (in Amps) that will flow through the cable. This can be calculated from the power rating of your equipment.
  2. Specify the cable length - The one-way distance (in meters) from your distribution board or consumer unit to the load.
  3. Select the voltage - Choose 230V for single-phase or 400V for three-phase installations.
  4. Choose the installation method - How the cable will be installed affects its current-carrying capacity due to different cooling conditions.
  5. Select conductor material - Copper is most common in UK installations. Aluminium has higher resistance but is lighter and cheaper for large cables.

Understanding the Results

  • Recommended Cable Size: The minimum cross-sectional area (in mm²) required for your installation
  • Voltage Drop: The voltage lost over the cable run as a percentage. Must be ≤5% for most circuits, ≤3% for lighting
  • Maximum Current: The current-carrying capacity of the selected cable with derating factors applied
  • Recommended MCB: The maximum circuit breaker rating suitable for the cable

BS 7671 Compliance Information

This calculator complies with BS 7671:2018+A2:2022 (18th Edition) - Requirements for Electrical Installations (IET Wiring Regulations). BS 7671 is the UK implementation of the harmonised international standard IEC 60364-5-52 (Selection and erection of electrical equipment — Wiring systems), so current-carrying capacities and voltage-drop methodology align with European and international practice.

Regulation 525 - Voltage Drop

Under normal service conditions, the voltage drop between the origin of the installation and the socket outlet or appliance shall not exceed:

  • 3% of the nominal voltage for lighting circuits
  • 5% of the nominal voltage for other circuits

Current-Carrying Capacity Considerations

The calculator applies derating factors for different installation methods as per Appendix 4 of BS 7671. Factors considered include:

  • Installation method (clipped direct, in conduit, etc.)
  • Ambient temperature (assumed 30°C)
  • Thermoplastic insulation (70°C rating)

Important: This calculator is a tool for initial sizing estimates. Final cable selection should be verified by a qualified electrician considering all installation-specific factors including grouping, thermal insulation, and harmonic currents.

Frequently Asked Questions

Free: BS 7671 Quick Reference Card

Max Zs values, diversity factors, cable ratings, voltage drop — one printable page. Plus occasional emails with calculator updates and useful tips.

Was this calculation helpful?

Complete Calculation Workflow

Follow this workflow for a complete electrical installation calculation: