Voltage Drop Calculator - BS 7671 Compliant

Calculate voltage drop and check BS 7671 compliance for electrical installations

Calculate Voltage Drop

Check if your cable installation meets BS 7671 voltage drop requirements

Amps

The current flowing through the cable

meters

One-way cable run distance

Cross-sectional area of the conductor

How to Calculate Voltage Drop UK - Complete Guide

Voltage drop calculation is essential for ensuring electrical installations comply with BS 7671 regulations. This guide explains the complete process for UK electrical systems.

Step 1: Understand BS 7671 Voltage Drop Limits

BS 7671 Regulation 525 specifies maximum voltage drop limits:

  • Lighting circuits: Maximum 3% of nominal voltage (230V × 3% = 6.9V maximum drop)
  • Other circuits: Maximum 5% of nominal voltage (230V × 5% = 11.5V maximum drop)
  • Three-phase systems: Measured line-to-line (400V system)

Step 2: Identify the Required Values

To calculate voltage drop, you need:

  • Cable length (L): One-way distance in meters from source to load
  • Design current (Ib): Maximum current the circuit will carry in Amps
  • Cable size: Cross-sectional area in mm²
  • mV/A/m value: From BS 7671 voltage drop tables (Table 4D5, 4E4A, etc.)
  • Phase type: Single-phase (230V) or three-phase (400V)

Step 3: Use the Voltage Drop Formula

The formula differs between single-phase and three-phase systems:

Single-Phase Formula:

Voltage Drop (V) = (mV/A/m × Length × Current) ÷ 1000

For 230V single-phase circuits (most domestic installations)

Three-Phase Formula:

Voltage Drop (V) = (mV/A/m × Length × Current × √3) ÷ 1000

For 400V three-phase circuits (commercial/industrial)

Then convert to percentage: (Voltage Drop ÷ Nominal Voltage) × 100

Step 4: Find mV/A/m Values from BS 7671 Tables

The millivolt drop per amp per meter (mV/A/m) is found in BS 7671 tables:

  • Table 4D5: Twin & earth cables (PVC insulated)
  • Table 4E4A: Single-core cables in conduit
  • Table 4D4A: SWA armoured cables
  • Table 4J4A: Mineral insulated cables

These values account for both conductor resistance and reactance at operating temperature.

Real-World Example: 32A Shower Circuit

Given: 32A shower, 15m cable run, 6mm² twin & earth, 230V

Step 1: From Table 4D5, 6mm² cable = 7.3 mV/A/m

Step 2: Calculate voltage drop:

Vd = (7.3 × 15 × 32) ÷ 1000 = 3.504V

Step 3: Convert to percentage:

(3.504 ÷ 230) × 100 = 1.52%

✓ Result: 1.52% is under the 5% limit - compliant with BS 7671

Common Mistakes to Avoid

  • Using cable length as return distance - always use one-way length
  • Forgetting to divide by 1000 (mV to V conversion)
  • Using incorrect mV/A/m values for the cable type
  • Not accounting for the √3 factor in three-phase calculations
  • Checking only current capacity and forgetting voltage drop

Voltage Drop Tables UK - mV/A/m Values BS 7671

Quick reference voltage drop values (mV/A/m) from BS 7671 for common UK cable types. These values are used in voltage drop calculations.

Twin & Earth Cable (6242Y) - Voltage Drop Values

Cable SizemV/A/mExample: 10m @ 20AMax Length @ 5%
1.0mm²44 mV/A/m8.8V (3.8%)26m @ 20A
1.5mm²29 mV/A/m5.8V (2.5%)40m @ 20A
2.5mm²18 mV/A/m3.6V (1.6%)64m @ 20A
4.0mm²11 mV/A/m2.2V (1.0%)52m @ 32A
6.0mm²7.3 mV/A/m1.46V (0.6%)79m @ 32A
10.0mm²4.4 mV/A/m0.88V (0.4%)87m @ 40A

Reference: BS 7671 Table 4D5 (2-core cables with protective conductor, 70°C thermoplastic)

SWA Cable - Voltage Drop Values

Cable SizemV/A/m (2-core)mV/A/m (3-core)Typical Use
2.5mm²18 mV/A/m18 mV/A/mGarden lighting
4.0mm²11 mV/A/m11 mV/A/mGarage sub-mains
6.0mm²7.3 mV/A/m7.3 mV/A/mEV chargers, outbuildings
10.0mm²4.4 mV/A/m4.4 mV/A/mLarge outbuildings
16.0mm²2.8 mV/A/m2.8 mV/A/mCommercial sub-mains

Reference: BS 7671 Table 4D4A (Armoured 70°C thermoplastic cables)

💡 Quick Tip: Lower mV/A/m values mean less voltage drop. For long cable runs, use larger cable sizes to reduce voltage drop and stay within BS 7671 limits.

Voltage Drop Calculation Examples - Step by Step

Follow these worked examples to understand voltage drop calculations for common UK installations.

132A Ring Main Circuit - 2.5mm² Cable

Scenario:

  • Circuit: 32A socket ring main
  • Cable: 2.5mm² twin & earth
  • Length: 28m (one leg of ring)
  • Load: 20A (typical maximum on one leg)

Calculation:

mV/A/m for 2.5mm² = 18 mV/A/m (Table 4D5)

Vd = (18 × 28 × 20) ÷ 1000 = 10.08V

Percentage = (10.08 ÷ 230) × 100 = 4.38%

✓ Result: 4.38% - Within 5% limit for power circuits

2Lighting Circuit - Checking 3% Limit

Scenario:

  • Circuit: 6A lighting circuit
  • Cable: 1.5mm² twin & earth
  • Length: 35m to furthest light
  • Load: 5A (LED lighting)

Calculation:

mV/A/m for 1.5mm² = 29 mV/A/m (Table 4D5)

Vd = (29 × 35 × 5) ÷ 1000 = 5.075V

Percentage = (5.075 ÷ 230) × 100 = 2.21%

✓ Result: 2.21% - Within 3% limit for lighting

3EV Charger Long Run - Voltage Drop Exceeds Limit

Scenario:

  • Circuit: 32A EV charger (7.4kW)
  • Cable: 6mm² SWA
  • Length: 40m to garage
  • Load: 32A continuous

Initial Calculation (6mm²):

mV/A/m for 6mm² SWA = 7.3 mV/A/m (Table 4D4A)

Vd = (7.3 × 40 × 32) ÷ 1000 = 9.344V

Percentage = (9.344 ÷ 230) × 100 = 4.06%

Upgrade to 10mm²:

mV/A/m for 10mm² SWA = 4.4 mV/A/m

Vd = (4.4 × 40 × 32) ÷ 1000 = 5.632V

Percentage = (5.632 ÷ 230) × 100 = 2.45%

✓ Solution: Upgrade to 10mm² SWA for 2.45% voltage drop

Note: 6mm² would work for runs under 28m at 32A

💡 Voltage Drop Calculation Tips

  • Always check before installation - voltage drop often requires larger cables than current capacity
  • Lighting circuits are stricter - 3% limit instead of 5%
  • For long runs, increase cable size to reduce voltage drop
  • Use the calculator above for quick verification of your calculations
  • Remember: One-way length, not return distance

How to Use the Voltage Drop Calculator

Use this calculator to verify that your cable installation meets BS 7671 voltage drop requirements before energizing the circuit.

  1. Enter the load current - The actual current (in Amps) flowing through the cable under normal operation.
  2. Specify the cable length - The one-way distance (in meters) from the distribution board to the load point.
  3. Select the cable size - The cross-sectional area of the conductor in mm² (e.g., 2.5mm², 4.0mm², etc.).
  4. Choose the voltage - 230V for single-phase or 400V for three-phase installations.
  5. Select conductor material - Copper is standard in the UK. Aluminium has higher resistance.

Understanding Voltage Drop

Voltage drop is the reduction in voltage that occurs as electrical current flows through a conductor due to the conductor's resistance. Excessive voltage drop can cause:

  • Poor performance of electrical equipment
  • Dimming of lights
  • Overheating of motors
  • Reduced equipment lifespan

BS 7671 Limits

  • Lighting circuits: Maximum 3% voltage drop
  • Other circuits: Maximum 5% voltage drop

BS 7671 Regulation 525 - Voltage Drop

This calculator checks compliance with BS 7671:2018+A2:2022 Regulation 525 - Voltage drop in consumers' installations.

Regulation 525.1

Under normal service conditions, the voltage drop between the origin of the installation (usually the supply terminals of the consumer unit) and any socket outlet or other point of utilization shall not exceed the values given in Appendix 12:

  • 3% for lighting circuits - To prevent visible dimming
  • 5% for other uses - Power circuits, heating, etc.

How Voltage Drop is Calculated

The calculator uses the following formula:

Single-phase: Vdrop = 2 × I × L × R
Three-phase: Vdrop = √3 × I × L × R

Where: I = Current (A), L = Length (m), R = Resistance (Ω/m)

Note: Voltage drop is only one consideration. Cable selection must also account for current-carrying capacity, overcurrent protection, and fault protection requirements.