Calculate voltage drop and check BS 7671 compliance for electrical installations
Check if your cable installation meets BS 7671 voltage drop requirements
Voltage drop calculation is essential for ensuring electrical installations comply with BS 7671 regulations. This guide explains the complete process for UK electrical systems.
BS 7671 Regulation 525 specifies maximum voltage drop limits:
To calculate voltage drop, you need:
The formula differs between single-phase and three-phase systems:
Single-Phase Formula:
For 230V single-phase circuits (most domestic installations)
Three-Phase Formula:
For 400V three-phase circuits (commercial/industrial)
Then convert to percentage: (Voltage Drop ÷ Nominal Voltage) × 100
The millivolt drop per amp per meter (mV/A/m) is found in BS 7671 tables:
These values account for both conductor resistance and reactance at operating temperature.
Given: 32A shower, 15m cable run, 6mm² twin & earth, 230V
Step 1: From Table 4D5, 6mm² cable = 7.3 mV/A/m
Step 2: Calculate voltage drop:
Vd = (7.3 × 15 × 32) ÷ 1000 = 3.504V
Step 3: Convert to percentage:
(3.504 ÷ 230) × 100 = 1.52%
✓ Result: 1.52% is under the 5% limit - compliant with BS 7671
Quick reference voltage drop values (mV/A/m) from BS 7671 for common UK cable types. These values are used in voltage drop calculations.
| Cable Size | mV/A/m | Example: 10m @ 20A | Max Length @ 5% |
|---|---|---|---|
| 1.0mm² | 44 mV/A/m | 8.8V (3.8%) | 26m @ 20A |
| 1.5mm² | 29 mV/A/m | 5.8V (2.5%) | 40m @ 20A |
| 2.5mm² | 18 mV/A/m | 3.6V (1.6%) | 64m @ 20A |
| 4.0mm² | 11 mV/A/m | 2.2V (1.0%) | 52m @ 32A |
| 6.0mm² | 7.3 mV/A/m | 1.46V (0.6%) | 79m @ 32A |
| 10.0mm² | 4.4 mV/A/m | 0.88V (0.4%) | 87m @ 40A |
Reference: BS 7671 Table 4D5 (2-core cables with protective conductor, 70°C thermoplastic)
| Cable Size | mV/A/m (2-core) | mV/A/m (3-core) | Typical Use |
|---|---|---|---|
| 2.5mm² | 18 mV/A/m | 18 mV/A/m | Garden lighting |
| 4.0mm² | 11 mV/A/m | 11 mV/A/m | Garage sub-mains |
| 6.0mm² | 7.3 mV/A/m | 7.3 mV/A/m | EV chargers, outbuildings |
| 10.0mm² | 4.4 mV/A/m | 4.4 mV/A/m | Large outbuildings |
| 16.0mm² | 2.8 mV/A/m | 2.8 mV/A/m | Commercial sub-mains |
Reference: BS 7671 Table 4D4A (Armoured 70°C thermoplastic cables)
💡 Quick Tip: Lower mV/A/m values mean less voltage drop. For long cable runs, use larger cable sizes to reduce voltage drop and stay within BS 7671 limits.
Follow these worked examples to understand voltage drop calculations for common UK installations.
Scenario:
Calculation:
mV/A/m for 2.5mm² = 18 mV/A/m (Table 4D5)
Vd = (18 × 28 × 20) ÷ 1000 = 10.08V
Percentage = (10.08 ÷ 230) × 100 = 4.38%
✓ Result: 4.38% - Within 5% limit for power circuits
Scenario:
Calculation:
mV/A/m for 1.5mm² = 29 mV/A/m (Table 4D5)
Vd = (29 × 35 × 5) ÷ 1000 = 5.075V
Percentage = (5.075 ÷ 230) × 100 = 2.21%
✓ Result: 2.21% - Within 3% limit for lighting
Scenario:
Initial Calculation (6mm²):
mV/A/m for 6mm² SWA = 7.3 mV/A/m (Table 4D4A)
Vd = (7.3 × 40 × 32) ÷ 1000 = 9.344V
Percentage = (9.344 ÷ 230) × 100 = 4.06%
Upgrade to 10mm²:
mV/A/m for 10mm² SWA = 4.4 mV/A/m
Vd = (4.4 × 40 × 32) ÷ 1000 = 5.632V
Percentage = (5.632 ÷ 230) × 100 = 2.45%
✓ Solution: Upgrade to 10mm² SWA for 2.45% voltage drop
Note: 6mm² would work for runs under 28m at 32A
Professional electricians need to understand these advanced concepts for complex installations and edge cases that affect voltage drop compliance.
The Electricity Safety, Quality and Continuity Regulations (ESQCR) 2002 define UK supply voltage limits that affect how you budget voltage drop.
| Nominal | Tolerance | Range |
|---|---|---|
| 230V | +10% / -6% | 216.2V to 253V |
| 400V (3-phase) | +10% / -6% | 376V to 440V |
The Critical Insight: If supply arrives at 216.2V (minimum allowed), a 5% installation drop leaves only 205.4V at the load. Many appliances specify minimum 207V operation. For critical loads, aim for 3-4% total drop, not 5%.
BS 7671 limits apply to total voltage drop from origin to load, not just the final circuit. For installations with sub-distribution boards, you must budget carefully.
Voltage Drop Budget Example:
Total allowed: 5% (11.5V)
Sub-main (meter to DB): 1.5% (3.45V)
Final circuit (DB to socket): 3.5% (8.05V)
Total: 5.0% ✓ Compliant
Common Mistake: Calculating final circuit drop without checking what drop already exists on the sub-main. A 40m sub-main at 100A on 25mm² cable already uses 2.1% of your budget.
The mV/A/m values in BS 7671 tables account for more than just conductor resistance. They include the complex impedance at operating temperature.
What mV/A/m Includes:
Temperature Correction:
For precise design calculations, BS 7671 Appendix 4 provides separate r (resistance) and x (reactance) components for complex impedance calculations.
Induction motors draw 6-8 times Full Load Current (FLC) during Direct-On-Line (DOL) starting. This causes temporary voltage drop that can affect starting performance.
| Running Vd | Starting Vd (×7) | Impact |
|---|---|---|
| 2% | 14% | Acceptable |
| 3% | 21% | Marginal |
| 5% | 35% | May stall |
Rule of Thumb: For motors, limit running voltage drop to 2-3% so starting drop stays under 20%. Use soft starters or VFDs for long cable runs.
For resistive loads (heaters, kettles), the simple mV/A/m calculation is accurate. For inductive loads (motors, transformers), power factor affects both current and voltage drop characteristics.
Impact on Design:
For accurate motor circuit design: Use the actual current (Watts ÷ Volts ÷ PF) not the theoretical resistive current, when calculating voltage drop.
EV chargers present unique voltage drop challenges because they operate at high current for extended periods, often at the end of long cable runs.
7.4kW Charger (32A)
22kW Charger (32A 3-phase)
OZEV grant regulations require voltage drop compliance certification. Oversizing cable avoids costly corrections and future-proofs for higher-power chargers.
Electric showers are particularly sensitive to voltage drop because the heating element output is proportional to V². A 5% voltage drop causes approximately 10% reduction in heating power.
Power Reduction Example (9.5kW shower):
At 230V:
9.5kW output
At 218.5V (5% drop):
8.55kW output (-10%)
At 210V (8.7% drop):
7.9kW output (-17%)
Recommendation: For electric showers, aim for maximum 3% voltage drop to maintain adequate hot water temperature, especially in winter.
When designing circuits, consider voltage drop early in the process:
Use this calculator to verify that your cable installation meets BS 7671 voltage drop requirements before energizing the circuit.
Voltage drop is the reduction in voltage that occurs as electrical current flows through a conductor due to the conductor's resistance. Excessive voltage drop can cause:
This calculator checks compliance with BS 7671:2018+A2:2022 Regulation 525 - Voltage drop in consumers' installations.
Under normal service conditions, the voltage drop between the origin of the installation (usually the supply terminals of the consumer unit) and any socket outlet or other point of utilization shall not exceed the values given in Appendix 12:
The calculator uses the following formula:
Where: I = Current (A), L = Length (m), R = Resistance (Ω/m)
Note: Voltage drop is only one consideration. Cable selection must also account for current-carrying capacity, overcurrent protection, and fault protection requirements.
Was this calculation helpful?
Follow this workflow for a complete electrical installation calculation:
Verify voltage drop compliance
You are here