MCB & RCBO Selector - BS 7671 Compliant

Select the correct MCB, RCBO, or RCD for your electrical circuit. Covers Type B, C, D curves with AFDD and SPD guidance per BS 7671:2018+A2:2022

MCB & RCBO Selection Calculator

Select the correct MCB, RCBO, or RCD for your circuit - BS 7671:2018+A2:2022 compliant

Select your circuit type for automatic recommendations

Circuit Details

Determines MCB curve type (B, C, or D)

Affects RCD requirements per BS 7671 special locations

RCBO recommended for all-RCBO consumer units

Special Requirements

MCB Types Explained (B, C, D)

Miniature Circuit Breakers (MCBs) are classified by their instantaneous magnetic trip characteristics per BS EN 60898-1. The three common types - B, C, and D - differ in how much overcurrent is needed to trigger the fast magnetic trip mechanism. Choosing the correct type prevents both nuisance tripping and inadequate protection.

Type B MCB - Magnetic Trip: 3-5 x In

The standard choice for domestic installations. Type B provides the most sensitive magnetic trip, activating between 3 and 5 times the rated current. This makes it ideal for circuits where high inrush currents are not expected.

Best For:
  • Lighting circuits (including LED)
  • General socket outlets in domestic installations
  • Resistive loads (heaters, immersion heaters, electric showers)
  • Long cable runs where higher earth loop impedance (Zs) is expected
  • EV chargers (resistive/electronic load characteristic)
Allowed Zs: Type B allows the highest earth fault loop impedance of the three types, making it suitable for circuits with long cable runs. For a 32A Type B MCB, maximum measured Zs = 1.15Ω.

Type C MCB - Magnetic Trip: 5-10 x In

The default choice for commercial and light industrial installations. Type C handles moderate inrush currents from inductive loads without nuisance tripping, while still providing adequate fault protection.

Best For:
  • Motors, pumps, fans, and compressors (5-8x inrush on DOL start)
  • Fluorescent lighting with magnetic ballasts
  • Air conditioning units with inverter compressors
  • Commercial socket circuits with mixed loads
  • Equipment with moderate inrush current
Note: Type C MCBs require lower Zs than Type B for the same rating. For a 32A Type C MCB, maximum measured Zs = 0.57Ω (half of Type B). This can limit maximum cable length.

Type D MCB - Magnetic Trip: 10-20 x In

A specialist choice for heavy industrial equipment with very high inrush currents. Type D is rarely used in domestic installations. Its high trip threshold means the earth fault loop impedance must be very low to ensure disconnection within 0.4 seconds.

Best For:
  • Large motors with high starting current (10-20x FLC)
  • Transformers (especially during energization)
  • Welding equipment with extreme inrush
  • X-ray machines and medical imaging equipment
  • Large capacitor banks
Warning: For a 32A Type D MCB, maximum measured Zs = 0.29Ω. This is extremely low and severely limits cable length. Always verify Zs compliance before specifying Type D.

Quick Selection Rule

  • Domestic installations: Type B for almost all circuits
  • Commercial installations: Type C for motor loads, Type B for socket/lighting
  • Industrial installations: Type C or D depending on motor inrush characteristics

Critical: The MCB rating (In) must satisfy the coordination rule: Ib In Iz, where Ib is the design current and Iz is the cable current-carrying capacity after derating. Also verify that Zs allows disconnection within the required time (0.4s for final circuits, 5s for distribution).

When to Use an RCBO

An RCBO (Residual Current Breaker with Overcurrent protection) combines an MCB and RCD in a single device. It provides both overcurrent protection and earth leakage detection for an individual circuit, which is the modern best practice for consumer unit design.

All-RCBO Consumer Units

The professional consensus has shifted toward all-RCBO configurations. Benefits include:

  • A fault on one circuit does not affect any other circuit
  • Easy fault diagnostics - only the affected RCBO trips
  • Maximum power availability and operational continuity
  • Each circuit has individual earth leakage protection
  • No risk of overloading a shared RCD with cumulative leakage

Dual RCD vs All-RCBO

Traditional dual RCD boards split circuits into two banks. A fault on one circuit trips the RCD for the entire bank, potentially affecting 6-8 circuits.

  • Dual RCD: Budget option, but a single fault can disconnect half the installation
  • High Integrity: Hybrid with some RCBOs for critical circuits (freezers, alarms)
  • All-RCBO: Best practice - each circuit independently protected
  • Main Switch Only: Flexible board for full RCBO population

Leakage Budget

BS 7671 Reg 531.3.2 states that standing earth leakage current should not exceed 30% of the RCD rated residual current. For a 30mA RCD, this means no more than 9mA of combined leakage from all circuits on that RCD. With modern LED drivers, dimmers, and electronic equipment, this budget is easily exceeded on shared RCDs - another strong reason to use individual RCBOs.

AFDD Requirements - BS 7671 AMD2

Arc Fault Detection Devices (AFDDs) use microprocessor technology to analyse the current waveform and identify the electronic signature of a dangerous arc fault. Standard MCBs and RCDs cannot detect series arc faults, which are a significant cause of electrical fires.

Mandatory Applications (Reg 421.1.7)

  • Houses in Multiple Occupation (HMOs): All final circuits supplying socket outlets up to 32A and lighting circuits
  • Purpose-built student accommodation: Same requirements as HMOs
  • Care homes and sheltered accommodation: All relevant final circuits
  • Buildings with sleeping accommodation above shops: Where fire risk assessment identifies the need

Recommended Applications

  • All domestic lighting circuits (highest arc fault fire risk)
  • Socket outlet circuits, especially where cables are in timber-framed walls
  • Circuits where cables pass through areas with combustible materials
  • Heating circuits with embedded elements (underfloor heating)

How AFDDs Work

AFDDs continuously monitor the circuit waveform using digital signal processing. They can distinguish between normal arcs (switch contacts, motor brushes) and dangerous arc faults (damaged cable, loose connections). When a dangerous arc pattern is detected, the AFDD disconnects the circuit within milliseconds. Modern AFDD/RCBO combination devices provide overcurrent, earth leakage, and arc fault protection in a single module.

RCD Selection Guide (Types AC, A, F, B)

BS 7671 Regulation 531.3.3 requires the RCD type to be specifically compatible with the waveforms generated by the connected equipment. Using an incorrect RCD type can result in the device being “blinded” by DC residual currents, preventing it from tripping during a genuine fault.

Type AC RCD - Restricted Use

Detects: Pure sinusoidal AC residual currents only (50Hz)
Cannot detect: Any DC component - can be blinded by modern electronics
Status: Heavily restricted in new installations. Not suitable for circuits with electronic equipment.
Limited use: Simple resistive loads only (tungsten lighting, electric showers with no electronic controls)

Type A RCD - Current Minimum Standard

Detects: AC sinusoidal + pulsating DC residual currents (up to 6mA smooth DC)
Status: Minimum standard for most modern installations
Applications: Socket outlets, LED lighting, domestic electronics, EV chargers (minimum)
Type A is the baseline for BS 7671:2018. Most domestic circuits should have at least Type A protection.

Type F RCD - Variable Speed Drives

Detects: All Type A waveforms + multi-frequency composite residual currents (up to 10mA smooth DC)
Required for: Equipment with variable speed drives (VSDs) and frequency inverters
Applications: Modern washing machines, dishwashers, air conditioning with inverter compressors

Type B RCD - Maximum Protection

Detects: All fault waveforms including smooth DC residual currents
Required for: Three-phase inverters, large PV systems, equipment with > 6mA DC leakage
Applications: EV chargers (preferred), solar PV installations, battery storage, medical equipment

Mandatory RCD Protection (BS 7671)

  • Socket outlets up to 32A: 30mA RCD (Reg 411.3.3)
  • Bathroom circuits: 30mA RCD (Section 701)
  • Outdoor circuits and equipment: 30mA RCD (Reg 411.3.3)
  • Cables buried less than 50mm deep: 30mA RCD
  • EV charging circuits: 30mA Type A minimum (Reg 722.531.2)
  • Swimming pool zones: 30mA RCD (Section 702)
  • Construction sites: 30mA RCD for socket outlets (Section 704)

Reference: BS 7671:2018+A2:2022 Section 411.3.3, 531.3.3, and Amendment 3:2024 for bidirectional device requirements.

Maximum Measured Zs Values - BS 7671

These are the maximum measured earth fault loop impedance values for 0.4 second disconnection time. The 80% temperature correction rule has been applied (i.e., these values are 80% of the BS 7671 Table 41.3 tabulated values, accounting for the increase in conductor resistance from ambient to operating temperature).

Rating (In)Type B Max Zs (Ω)Type C Max Zs (Ω)Type D Max Zs (Ω)
6A6.133.061.53
10A3.681.840.92
16A2.301.150.57
20A1.840.920.46
25A1.470.730.37
32A1.150.570.29
40A0.920.460.23
50A0.730.360.18
63A0.580.290.14

Reference: BS 7671 Table 41.3 with 80% temperature correction applied (NICEIC/IET guidance). Values shown are for 0.4s disconnection at ambient temperature measurement.

Why the 80% Rule?

Zs is typically measured during initial verification when the installation is at ambient temperature (approximately 20°C). However, the BS 7671 limits are set for when conductors are at their full operating temperature (70°C for PVC). Since copper resistance increases with temperature, a value measured at 20°C must not exceed 80% of the tabulated maximum to ensure compliance at operating temperature.

Common UK Circuit Protection Quick Reference

Typical MCB/RCBO specifications for standard UK residential circuits. These are starting points - always verify for your specific installation conditions.

CircuitMCB RatingTypeCableRCD Required
Lighting6AB1.0-1.5mm²Recommended
Ring Final (Sockets)32AB2.5mm²Mandatory (30mA)
Radial Sockets (20A)20AB2.5mm²Mandatory (30mA)
Immersion Heater16AB2.5mm²Recommended
Boiler6-16AB1.5-2.5mm²Recommended
Cooker (up to 10kW)32AB6mm²If cooker control has socket
Shower (8.5kW)40AB6mm²Mandatory (bathroom)
Shower (9.5kW+)50AB10mm²Mandatory (bathroom)
EV Charger (7.4kW)32AB6mm² SWAMandatory (30mA Type A min)
Hot Tub (32A)32AC6mm² SWAMandatory (outdoor)
Outbuilding Sub-main32-63AB6-10mm² SWAMandatory (30mA at sub-board)

Important: These are typical domestic values. Always calculate cable size for your specific installation considering cable length, installation method, ambient temperature, grouping, and thermal insulation contact. Use the calculator above for accurate MCB/RCBO selection.

MCB Coordination Rule: Ib In Iz

The fundamental safety principle of BS 7671 circuit protection is the coordination between the design current, the protective device rating, and the cable capacity. This ensures the cable is always protected by the MCB.

Design Current
Ib

Maximum current the circuit carries under normal operating conditions

Device Rating
In

Rated current of the MCB/RCBO (must be Ib)

Cable Capacity
Iz

Current-carrying capacity of the cable after applying all derating factors

Worked Example

Scenario: 9.5kW electric shower, 6mm² twin and earth cable clipped direct

  • Ib = 9500W ÷ 230V = 41.3A (design current)
  • In = 50A Type B MCB (next standard rating above 41.3A)
  • Iz = 64A (10mm² T&E clipped direct from Table 4D5)

Check: 41.3A (Ib) 50A (In) 64A (Iz) - PASS

Note: 6mm² cable (Iz = 47A) would fail because In (50A) > Iz (47A). The cable must be upgraded to 10mm² to satisfy coordination.

Was this calculation helpful?