Immersion Heater Circuit Calculator

Size the cable, MCB and isolator for a dedicated immersion heater circuit to BS 7671.

Immersion Heater Circuit Calculator

Size the cable, MCB and isolator for a dedicated immersion heater circuit to BS 7671.

kW

Most UK immersion heaters are 3 kW

m

Immersion heater circuits

A standard 3 kW immersion heater draws about 13 A and must be supplied by its own dedicated radial circuit with a 20 A double-pole switch (or a DP pull-cord in a bathroom). The cable is sized so its installed current-carrying capacity — after ambient and installation-method correction — is at least the MCB rating, and the voltage drop stays within 5%.

For a complete installation, also check the earth fault loop impedance with the Max Zs calculator.