Prospective Fault Current (PFC) Calculator

Calculate Prospective Short Circuit Current (PSCC) and Prospective Earth Fault Current (PEFC) according to BS 7671 Regulation 612.11. Determine protective device breaking capacity requirements.

Prospective Fault Current Calculator

Calculate Prospective Short Circuit Current (PSCC) and Prospective Earth Fault Current (PEFC) according to BS 7671 Regulation 612.11. Results help determine required breaking capacity of protective devices.

Earthing arrangement

Single or three-phase supply

Ω

From EICR or DNO data

Ω

Circuit line and CPC resistance (leave blank for PSCC only)

Typical Ze Values (for reference)
TN-S (Separate neutral and earth)

Typical: 0.8Ω

Range: 0.35Ω - 0.8Ω

Cable sheath used as protective conductor

TN-C-S (PME - Protective Multiple Earthing)

Typical: 0.35Ω

Range: 0.1Ω - 0.35Ω

Combined neutral and earth (PEN) from supplier

TT (Local earth electrode)

Typical: 21Ω

Range: 5Ω - 200Ω

Highly variable depending on earth electrode resistance

Understanding Prospective Fault Current

Prospective Fault Current (PFC) is the maximum current that would flow in the event of a fault with negligible impedance. It's a critical safety parameter that must be determined to ensure protective devices can safely interrupt fault currents without damage or danger. BS 7671 Regulation 612.11 requires PFC to be measured, calculated, or determined for all installations.

PSCC

Prospective Short Circuit Current is the maximum current that would flow during a line-to-neutral (single-phase) or line-to-line (three-phase) short circuit. Calculated as PSCC = U₀ / Ze.

PEFC

Prospective Earth Fault Current is the maximum current that would flow during a line-to-earth fault. Calculated as PEFC = U₀ / Zs, where Zs = Ze + (R₁ + R₂).

PFC (Maximum)

The Prospective Fault Current is taken as the higher value of PSCC or PEFC. This determines the minimum breaking capacity (Icn) required for protective devices.

BS 7671 Requirements

  • Regulation 612.11: Prospective fault current shall be measured, calculated or determined by another method at the origin and at other relevant points of the installation
  • Regulation 536.1: Every protective device shall have adequate breaking capacity. A device with inadequate breaking capacity may be used if backed up by another device with the necessary breaking capacity
  • Verification: PFC must be verified during initial verification (Regulation 611.3) and periodic inspection and testing
  • Documentation: PFC values must be recorded on Electrical Installation Certificates (EIC) and Electrical Installation Condition Reports (EICR)

Protective Device Breaking Capacity (Icn)

The breaking capacity (Icn rating) of a protective device is its ability to safely interrupt fault currents. The device's breaking capacity must exceed the prospective fault current at its point of installation.

Device TypeBreaking Capacity (Icn)Typical ApplicationStandard
Standard MCB6kA (6,000A)Domestic installationsBS EN 60898
Enhanced MCB10kA (10,000A)Commercial installationsBS EN 60898
MCCB25kA - 50kAIndustrial installationsBS EN 60947-2
BS 88 Fuse80kA+Main switchgearBS 88

Important Safety Considerations

  • ⚠️ Always Verify: PFC should be measured during testing, not just calculated. Calculated values may differ from actual site conditions
  • ⚠️ Margin of Safety: Select devices with breaking capacity exceeding PFC by at least 10% for safety margin
  • ⚠️ Back-Up Protection: Devices with inadequate breaking capacity may be used if backed up by a suitable device upstream (Regulation 536.1)
  • ⚠️ TT Systems: In TT systems, RCD protection is mandatory. PEFC is limited by earth electrode resistance
  • ⚠️ Distribution Networks: PFC can change if supply authority makes network modifications. Periodic testing is essential

Measurement vs Calculation

Measurement (Preferred)

  • ✓ Most accurate method
  • ✓ Uses PFC test instrument
  • ✓ Accounts for all parallel paths
  • ✓ Reflects actual site conditions
  • ✓ Required for certification

Calculation

  • • Useful for design stage
  • • Based on measured Ze
  • • May not account for all factors
  • • Should be verified by testing
  • • Can be conservative or optimistic

Example Calculation

Given:

  • • System: TN-C-S (PME)
  • • Ze: 0.35Ω (typical PME value)
  • • Circuit R₁+R₂: 0.65Ω (32A ring, 80m of 2.5/1.5mm²)
  • • Voltage: 230V (single-phase)

Calculations:

  • • PSCC = 230V / 0.35Ω = 657A
  • • Zs = 0.35Ω + 0.65Ω = 1.0Ω
  • • PEFC = 230V / 1.0Ω = 230A
  • • PFC = max(657A, 230A) = 657A

Device Selection:

Standard 6kA MCB is suitable (6,000A > 657A)

Three-Phase Considerations

For three-phase systems, the prospective fault current can be higher during three-phase faults:

  • Single-Phase PSCC: Line-to-neutral fault = U₀ / Ze (where U₀ = 230V)
  • Three-Phase PSCC: Line-to-line-to-line fault ≈ √3 × single-phase PSCC
  • Line-to-Line Voltage: 400V between phases (√3 × 230V)
  • Device Selection: Ensure MCCBs are rated for three-phase fault currents

Complete UK Prospective Fault Current Technical Guide

In-depth technical reference covering fault loop physics, testing methodology, breaking capacity standards, and the regulatory requirements UK electricians must understand for BS 7671 compliance.

The Physics: Why I = U/Z Matters

The magnitude of any fault current is governed by Ohm's Law for AC circuits:Ipf = U0 / Zs

Ipf

Prospective Fault Current in Amperes - the current that would flow if no protective device interrupted it

U0

Nominal voltage to earth: 230V for single-phase, 400V line-to-line for three-phase

Zs

Total fault loop impedance - includes supply transformer, DNO cables, meter tails, and installation wiring

Critical insight: Because voltage is fixed (~230V), fault current is inversely proportional to impedance. Lower impedance = higher fault current. This is why PFC is always highest at the origin of an installation, before cable resistance dampens it.

PSCC vs PEFC: Understanding What You're Measuring

BS 7671 distinguishes between two specific fault conditions. Both must be assessed, and the higher value is recorded as the PFC for the installation.

Prospective Short-Circuit Current (PSCC)

The overcurrent resulting from a fault between live conductors:

  • Single-phase: Fault between Line and Neutral
  • Three-phase: Fault between two or all three Lines

Test: L-N measurement

Prospective Earth Fault Current (PEFC)

The overcurrent resulting from a fault between a live conductor and earth:

  • • Fault between Line and exposed-conductive-part
  • • Fault between Line and Main Earthing Terminal (MET)

Test: L-E measurement

⚠️ Record the HIGHER value as the installation PFC

This ensures protective devices are rated for the absolute worst-case fault scenario.

How Earthing System Affects Your PFC Reading

SystemTypical ZePSCC vs PEFCPractical Impact
TN-S0.35-0.8ΩPSCC often higher than PEFC (cable sheath/armour has higher resistance than neutral)Both tests required - don't assume L-E is higher
TN-C-S (PME)0.1-0.35ΩPSCC and PEFC typically identical (PEN conductor serves both returns)Low impedance = high fault currents; check breaking capacity carefully
TT10-200Ω+PSCC is high (metal L-N path); PEFC is very low (earth electrode resistance)Still verify PSCC for MCB rating! RCDs handle earth faults, but L-N faults can be kA range

TT system trap: Don't record low PEFC (e.g., 20A) as your PFC. The PSCC between Line and Neutral can still be thousands of amperes if the transformer is close - that's what determines MCB breaking capacity.

Single-Phase Testing Sequence (BS 7671 Compliant)

Step-by-Step Procedure

  1. 1Prepare: Ensure main switch is OFF (installation isolated), but supply side remains live
  2. 2Keep bonding connected: Unlike Ze testing, measure with earthing and bonding IN PLACE. Parallel earth paths lower impedance, giving worst-case (highest) PFC
  3. 3Test L-N (PSCC): Connect tester between Line and Neutral at incoming terminals. Record as IL-N
  4. 4Test L-E (PEFC): Connect tester between Line and Main Earthing Terminal. Record as IL-E
  5. 5Record: The higher of IL-N or IL-E is your PFC

Instrument Settings

✓ Use "High Current" mode

At the origin (upstream of RCDs), High Current mode provides more accurate low-impedance readings with less electrical noise

CAT III/IV rated instrument

Test instruments must be rated to CAT III 300V/600V minimum for supply intake testing

Null test leads first

Lead resistance (0.05-0.10Ω) must be zeroed out - see common mistakes section

Three-Phase PFC: The Doubling Rule & 0.87 Factor

Testing three-phase supplies involves 400V measurements. Not all loop testers are rated for line-to-line connection. These methods allow safe estimation using single-phase readings.

Method A: The Doubling Rule (Safe)

IET On-Site Guide recommended method using standard single-phase tester.

  1. 1. Measure PSCC (L-N) for each phase individually
  2. 2. Identify the highest single-phase reading
  3. 3. Multiply by 2

Highest L-N = 3.0kA
Three-phase PFC = 3.0 × 2 = 6.0kA

Conservative estimate with good safety margin

Method B: The 0.87 Factor (Precision)

For industrial installations where the doubling rule might unnecessarily condemn equipment.

  1. 1. Use 400V-rated tester to measure L-L impedance
  2. 2. Divide the L-L fault current by 0.87

Ipf(3ph) = IL-L(measured) ÷ 0.87

The 0.87 factor (≈√3/2) accounts for vector relationship in balanced three-phase faults. Guidance Note 3 method.

The 16kA Conditional Rating: Why 6kA MCBs Work with 10kA PFC

A common question: "PFC measured at 8kA but the consumer unit has 6kA MCBs - is this safe?" The answer lies in BS EN 61439-3 Annex ZB.

The 16kA Conditional Rating Explained

Domestic consumer units can be rated at 16kA conditional, allowing 6kA MCBs to be used with fault currents up to 16kA, provided:

  • 1.Protected upstream by a cutout fuse to BS 88-3 (or BS 1361 Type II)
  • 2.Upstream fuse rating does not exceed 100A
  • 3.Consumer unit is a manufacturer-tested assembly (no brand mixing)

How Backup Protection Works

The BS 88-3 service fuse is extremely fast-acting at high fault currents. In a 10kA fault, the fuse operates so quickly that its energy let-through (I²t) is within what the 6kA MCB can withstand without damage.

When This Doesn't Apply

  • • Commercial installations with MCCB upstream
  • • Fuses larger than 100A
  • • Mixed-brand consumer units
  • • Sub-distribution boards without fuse backup

In these cases, MCBs must be individually rated for full PFC

Attenuation: How Cable Resistance Reduces PFC

Fault current drops rapidly through conductor resistance. Even a few meters of cable can significantly reduce PFC at a distribution board - this is why measuring at sub-boards often allows lower-rated (cheaper) breakers to be used.

Cable Resistance Reference (Copper at 20°C)

16mm²

1.15 mΩ/m

25mm²

0.727 mΩ/m

35mm²

0.524 mΩ/m

50mm²

0.387 mΩ/m

Remember: Total loop = Line + Neutral/Earth (double the run length)

Worked Example: Meter Tail Attenuation

At DNO Intake:

  • Ze = 0.015Ω
  • PFC = 230 ÷ 0.015 = 15.3kA
  • (Exceeds 10kA MCB rating!)

After 5m of 25mm² Tails:

  • Added R = 10m × 0.000727 = 0.00727Ω
  • Total Z = 0.015 + 0.00727 = 0.02227Ω
  • PFC = 230 ÷ 0.02227 = 10.3kA

Result: Just 5 meters of tails reduced PFC by 5kA. With 10m of tails (20m conductor path), PFC drops to 7.8kA.

This explains why faults at socket outlets are rarely a breaking capacity issue - the resistance of 2.5mm² T&E decimates fault current within meters of the consumer unit.

DNO Declared Maximum vs What You'll Actually Measure

DNOs declare standard maximum fault levels to cover future network reinforcements. These are design worst-case values, not what you'll typically measure.

DNO Declared Maximums

  • Single-phase (up to 100A): 16kA
  • Three-phase: 25kA

Use these values if measurement is impossible (e.g., design stage for new build)

Typical Measured Values

  • Domestic TN-S/TN-C-S: Ze 0.10-0.35Ω → PFC 650A-2.3kA
  • TT systems: PEFC negligible (earth electrode), but PSCC can still be kA range
  • Central London/city centres: Can genuinely approach 16kA due to very short service cables

Urban hazard: In dense city areas, substations may be in building basements. With extremely short service cables, Ze can approach 0.01-0.02Ω, genuinely reaching 16kA+. Even residential blocks in these areas may need industrial-grade switchgear.

⚠️ The PME Upgrade Hazard: Why Old Consumer Units Become Dangerous

Many older properties were connected via TT or TN-S systems with high impedance. When DNOs upgrade networks to PME (TN-C-S), impedance drops dramatically - potentially making legacy breakers dangerous.

Progression Example

Original (TN-S)

Ze = 0.8Ω

PFC = 287A

BS 3871 M3 (3kA) ✓ Safe

After PME Conversion

Ze = 0.2Ω

PFC = 1,150A

M3 (3kA) ✓ Still safe

New Substation 50m Away

Ze = 0.05Ω

PFC = 4,600A

M3 (3kA) ✗ DANGEROUS

Why recording PFC on EICRs matters: It tracks degradation of safety margins over time. An inspector seeing PFC increase from 1.5kA to 3.2kA across inspections can identify that the BS 3871 M4.5 breakers are now operating near their limit - before a fault proves it catastrophically.

Common PFC Testing Mistakes That Can Get You in Trouble

Mistake 1: Recording "16kA" Instead of Measured Value

Some inspectors measure 1.2kA but record "16kA" because "that's what the DNO says." This creates a contradiction if you're justifying keeping 3kA/4.5kA legacy breakers - the certificate states PFC (16kA) exceeds device rating (3kA), which technically triggers a C2 (Potential Danger) code.

Best practice: Record the measured value. Note DNO declared maximum in observations if significantly higher, warning that future upgrades could affect compliance.

Mistake 2: Failing to Null Test Leads

Test lead resistance (typically 0.05-0.10Ω) gets added to your reading if not zeroed. This makes measured Ze appear higher than reality → calculated PFC appears lower than reality.

This is a "fail-to-danger" error - you think you're safe when you're not.

Mistake 3: Using "No-Trip" Mode at Origin

"No-Trip" (low current) loop settings are for testing downstream of RCDs to avoid nuisance tripping. At the origin (upstream of RCDs), "High Current" mode gives cleaner, more accurate low-impedance readings with less electrical noise.

Mistake 4: Only Testing L-E (PEFC)

Especially in TT systems, electricians often only test L-E and record the low value. The PSCC (L-N) could be significantly higher and is what determines whether the MCB can safely interrupt a short-circuit between live conductors.

Always test both L-N and L-E, record the higher value.

Legacy MCB Breaking Capacity Reference (BS 3871)

When inspecting older installations, you may encounter obsolete BS 3871 MCBs. Their "M" ratings correspond to these breaking capacities:

M RatingBreaking CapacityStatus
M11kA (1,000A)Often inadequate today
M1.51.5kA (1,500A)Often inadequate today
M33kA (3,000A)Verify against measured PFC
M4.54.5kA (4,500A)Verify against measured PFC
M66kA (6,000A)Usually acceptable
M99kA (9,000A)Usually acceptable

EICR coding: If measured PFC exceeds the M-rating of installed BS 3871 MCBs, this is typically a C2 (Potentially Dangerous) code requiring urgent attention. The consumer unit should be upgraded to modern BS EN 60898 devices with appropriate breaking capacity.

Was this calculation helpful?