Earthing & Bonding Calculator - BS 7671 Compliant

Calculate main earthing conductors, protective bonding conductors, and circuit protective conductors (CPC) according to British Standards BS 7671:2018

Main Earthing Conductor Size (Table 54.7)

Calculate the minimum size of the main earthing conductor based on the line conductor size

Size of the incoming supply line conductor

About Earthing & Bonding Calculations

Proper earthing and bonding are critical safety requirements in all UK electrical installations. This calculator helps electricians and electrical engineers determine the correct conductor sizes according to BS 7671:2018 regulations.

Main Earthing Conductor

Sized using Table 54.7 based on the line conductor size. For line conductors ≤16mm², the earth conductor must be the same size. For conductors >35mm², it can be half the size.

Regulation 543.1.4

Main Protective Bonding

For PME (TN-C-S) systems, use Table 54.8 based on PEN conductor size. For TN-S and TT systems, bonding is half the main earthing conductor size (minimum 6mm², maximum 25mm² if mechanically protected).

Regulation 544.1.1 & Table 54.8

CPC (Adiabatic Equation)

Circuit protective conductors are sized using the adiabatic equation: S = √(I²t) / k, where I is fault current, t is disconnection time, and k is a factor based on conductor material and insulation.

Regulation 543.1.3

BS 7671:2018 Tables Used

Earthing & Bonding

  • • Table 54.7 - Minimum earthing conductor sizes
  • • Table 54.8 - Main protective bonding for PME
  • • Table 54.2 - k values for separate bare conductors
  • • Table 54.3 - k values for conductors in cables

k Values

  • • Copper 70°C PVC: k = 115 (30°C) or 103 (70°C)
  • • Copper 90°C XLPE: k = 143 (30°C) or 134 (90°C)
  • • Aluminium 70°C PVC: k = 76 (30°C) or 68 (70°C)
  • • Aluminium 90°C XLPE: k = 94 (30°C) or 88 (90°C)

When to Use This Calculator

Main Earthing:

  • ✓ Designing new electrical installations
  • ✓ Upgrading consumer units
  • ✓ Checking existing earthing adequacy
  • ✓ Commercial and industrial installations

Main Bonding:

  • ✓ PME (TN-C-S) supply connections
  • ✓ Bonding water and gas services
  • ✓ Oil tank bonding
  • ✓ Structural steelwork bonding

Important Notes

  • ⚠️ PME Systems: Contact your Distribution Network Operator (DNO) to confirm the PEN conductor size for Table 54.8 calculations.
  • ⚠️ Minimum Sizes: Main protective bonding conductors must be at least 6mm² (non-PME) or 10mm² (PME), regardless of calculations.
  • ⚠️ Adiabatic Equation: Only applies where disconnection time does not exceed 5 seconds. For longer times, use alternative calculation methods.
  • ⚠️ Professional Advice: These calculations are for guidance. Always consult BS 7671:2018+A2:2022 and seek professional electrical engineer advice for complex installations.

Complete UK Earthing & Bonding Technical Guide

BS 7671:2018+A2:2022 requirements for earthing and bonding are critical for installation safety. This guide covers the regulatory framework, calculation methods, and practical applications.

UK Earthing System Types - TN-S, TN-C-S (PME), and TT

The DNO provides different earthing arrangements, each with unique impedance characteristics and safety implications for bonding conductor sizing.

SystemEarth PathMax ZeMin Bonding
TN-SSeparate conductor (cable sheath)0.8Ω6mm² min
TN-C-S (PME)Combined PEN conductor0.35Ω10mm² min (Table 54.8)
TTLocal earth electrode21Ω (variable)6mm² min

PME "Open PEN" Risk: In TN-C-S systems, if the PEN conductor is severed in the street, neutral current seeks alternative paths through your bonding conductors. This is why PME bonding sizes (Table 54.8) are larger - they must carry diverted network current without overheating.

Amendment 2: The "Plastic Pipe" Exception - When NOT to Bond

A critical update in Amendment 2 changed the approach to bonding. Regulation 411.3.1.2 now states that metallic pipes entering the building with an insulating section at entryneed not be bonded.

The 22kΩ Test: To determine if a metallic part requires bonding, measure resistance between the part and the MET:

  • R > 22kΩ: Not extraneous - DO NOT bond
  • R ≤ 22kΩ: Extraneous - bonding required

Technical Rationale: Modern utilities use polyethylene (MDPE) service pipes. Internal copper plumbing isolated from earth is not "extraneous" - it doesn't introduce earth potential. Bonding such isolated systems is unnecessary and potentially hazardous: in a broken PEN scenario, bonding would export dangerous voltage to taps and radiators.

Practical Check: If the water/gas service pipe is plastic at the property boundary and the internal copper has no contact with earth (verified by 22kΩ test), bonding is not required. Document your test result on the EIC/EICR.

Table 54.8 - PME Main Protective Bonding Conductor Sizes

For PME (TN-C-S) installations, bonding conductor sizes are determined by the supply neutral (PEN) conductor size, not the earthing conductor size. This ensures the bonding can carry diverted network current safely.

Supply Neutral SizeMin Bonding (Copper)Typical Application
Up to 35mm²10mm²Most domestic (25mm² tails)
35mm² to 50mm²16mm²Large domestic / small commercial
50mm² to 95mm²25mm²Commercial installations
95mm² to 150mm²35mm²Industrial
Over 150mm²50mm²Large industrial

Common Domestic Scenario: Most UK PME supplies have 25mm² meter tails. The supply neutral is also 25mm² (within the "up to 35mm²" range), so main bonding must be minimum 10mm² to gas and water.

Using SWA Armour as the CPC - Adiabatic Verification

In commercial installations using Steel Wire Armoured (SWA) cable, the armour often serves as the CPC. However, steel has a much lower k value than copper, meaning it handles fault energy less efficiently.

k Values Comparison:

  • Copper/PVC (70°C): k = 115
  • Copper/XLPE (90°C): k = 143
  • Steel armour/PVC: k = 51
  • Steel armour/XLPE: k = 46

Practical Impact:

The lower k value (46-51 vs 115-143) means steel armour must be physically larger to provide the same protection as copper. Always verify armour adequacy using the adiabatic equation with manufacturer CSA data.

Table 54.7 (selection method) often suggests armour is insufficient, but adiabatic calculation usually validates it because modern breakers clear faults so quickly that the I²t energy is low.

Earth Fault Loop Impedance (Zs) - The 80% Rule

Verification of Zs proves your earthing system works. The loop impedance must be low enough to guarantee protective device operation within required times (0.4s or 5s).

Zs = Ze + (R1 + R2)

The 80% Design Rule: BS 7671 tables assume cables at maximum operating temperature (70°C). Testing at ambient temperature gives lower readings. Apply the 80% rule during verification:

  • • Design limit (Table 41.3): e.g., 1.37Ω for 32A Type B
  • • Test limit: 1.37 × 0.8 = 1.096Ω maximum measured
MCB RatingType B Max ZsType C Max ZsType D Max Zs
16A2.73Ω1.37Ω0.68Ω
32A1.37Ω0.68Ω0.34Ω
63A0.70Ω0.35Ω0.17Ω

Values from BS 7671 Table 41.3 (incorporating Cmin = 0.95)

Bathroom Supplementary Bonding - When Can It Be Omitted?

Regulation 701.415.2 allows supplementary bonding in bathrooms to be omitted if all three conditions are met:

Condition 1

All final circuits have additional protection by 30mA RCDs

Condition 2

All extraneous-conductive-parts are connected to main protective bonding

Condition 3

Disconnection times (ADS) are met for all circuits

In modern domestic installations with full RCD protection and proper main bonding, supplementary bonding is rarely required. However, it remains common in older properties without RCDs.

EV Charging and PME - Section 722 Restrictions

PME earthing presents specific hazards for outdoor EV charging points. Regulation 722.411.4.1 restricts PME use for outdoor EV installations.

The Risk: A broken PEN in the street can raise the car chassis to 230V relative to the ground the user is standing on. Since users touch the car while standing on earth, this creates an electrocution hazard.

Solutions:

  • Install the EV charger as a TT island with its own earth electrode
  • Use a PME fault detection device that disconnects L, N, and E on fault
  • For enclosed garages, PME may be acceptable (user not standing on true earth)

Common EICR Codes for Earthing & Bonding Defects

C2: Undersized Bonding on PME

6mm² bonding on a PME supply where Table 54.8 requires 10mm². Potentially dangerous - bonding cannot safely carry diverted neutral current.

C2: No Supplementary Bonding (No RCDs)

Older property with rewirable fuses, no RCDs, and no supplementary bonding in bathroom. The omission conditions are not met.

C3: Inaccessible Earth Connection

Connection to earth electrode is buried or corroded. BS 7671 requires accessible connections for inspection (except exothermic welds).

C3: Bonding to Plastic Pipes

Bonding conductor connected to internal copper with plastic supply pipe. Unnecessary per Amendment 2 - verify with 22kΩ test and remove if appropriate.

Professional References

  • BS 7671:2018+A2:2022 - Requirements for Electrical Installations
  • IET Guidance Note 5 - Protection Against Electric Shock
  • IET On-Site Guide - Quick reference tables for Zs values
  • ESQCR 2002 - Electricity Safety, Quality and Continuity Regulations

Frequently Asked Questions

What is the difference between earthing and bonding?

Earthing connects exposed conductive parts of electrical equipment to the main earthing terminal, providing a path for fault current. Bondingconnects extraneous conductive parts (pipes, steelwork) to ensure they remain at the same electrical potential, preventing dangerous voltage differences.

What is PME and why does it affect bonding size?

PME (Protective Multiple Earthing) or TN-C-S is a supply system where the neutral and earth are combined in the supply network. PME requires larger bonding conductors (Table 54.8) because if the neutral is lost, dangerous voltages can appear on bonded metalwork.

What is the adiabatic equation used for?

The adiabatic equation (S = √(I²t) / k) calculates the minimum size of circuit protective conductors (CPC) to withstand fault current for the disconnection time without thermal damage. It assumes all heat remains in the conductor (adiabatic heating).

Can I use aluminium for earthing conductors?

Aluminium can be used but has lower conductivity than copper, requiring larger conductor sizes. Copper is more common due to better conductivity, corrosion resistance, and ease of termination. Always use appropriate connectors for aluminium.

Find Electrical Distributors Near You

Looking for earthing and bonding products? Browse our directory of electrical distributors across London carrying leading cable brands.

View All Distributors

Frequently Asked Questions

Was this calculation helpful?