Earth Fault Loop Impedance (Zs) Calculator

Calculate actual earth fault loop impedance from Ze + R1+R2. Verify compliance with BS 7671 maximum Zs values and determine if your protective device will disconnect within the required time.

Calculate Earth Fault Loop Impedance (Zs)

Calculate actual Zs from Ze + R1+R2 and verify compliance with BS 7671 maximum values

Ω

Measured at the origin of the installation. Typical: 0.35 (TN-C-S), 0.8 (TN-S)

Ω

Combined resistance of line conductor (R1) and CPC (R2) at 20 degrees C. Measured or from BS 7671 tables.

Protective Device

Magnetic trip at 3-5× rated current. Most common for lighting and socket circuits.

Rated current of the protective device

0.4s required for most socket and lighting circuits. 5s allowed for distribution circuits.

What is Earth Fault Loop Impedance?

Earth fault loop impedance (Zs) is the total impedance of the fault current path from the point of an earth fault, through the earth fault loop, back to the source of supply. It determines how much fault current will flow during an earth fault and therefore whether the protective device (MCB, fuse, or RCBO) will disconnect the supply quickly enough to prevent electric shock.

The earth fault loop impedance is made up of two components: Ze (the external earth fault loop impedance provided by the supply network) and R1+R2 (the resistance of the circuit's line conductor and circuit protective conductor). The fundamental formula is: Zs = Ze + (R1 + R2).

Zs Formula

Zs = Ze + (R1 + R2)

  • Ze - External earth fault loop impedance (from DNO supply)
  • R1 - Resistance of the line conductor
  • R2 - Resistance of the circuit protective conductor (CPC)

PEFC Formula

PEFC = U0 / Zs

Where U0 = 230V for single-phase UK supply. The PEFC (Prospective Earth Fault Current) determines if the protective device can disconnect within the required time.

How Zs Affects Safety

The earth fault loop impedance directly controls the fault current magnitude. A lower Zs means higher fault current, which makes protective devices operate faster. BS 7671 sets maximum Zs values for each type and rating of protective device to ensure disconnection within the required time.

Circuit TypeMax Disconnection TimeApplies To
TN Final Circuits0.4 secondsSocket outlets, portable equipment, lighting
TN Distribution Circuits5 secondsSub-main cables, distribution boards
TT Final Circuits0.2 secondsAll circuits (RCD protection mandatory)

Testing vs Calculating Zs

Calculation Method

Measure Ze at the origin and R1+R2 using a low-resistance ohmmeter during dead testing, then add them: Zs = Ze + (R1+R2). This method is preferred by NICEIC as it gives more consistent, repeatable results.

Direct Measurement

Use a loop impedance tester at the furthest point of the circuit. Faster but can be affected by supply fluctuations and electrical noise. High-current testers give best accuracy but will trip RCDs.

The 80% Rule Explained

BS 7671 Table 41.3/41.4 values assume conductors at their maximum operating temperature (70°C for PVC). When you test at ambient temperature (~20°C), resistance is approximately 20% lower.

The 80% rule accounts for this: your measured or calculated Zs (at 20°C) should not exceed 80% of the tabulated maximum. This ensures compliance even when cables heat up under load.

Testing Limit = Max Zs (table) x 0.80

Example: 32A Type B MCB, Max Zs = 1.37Ω, Testing limit = 1.37 x 0.80 = 1.10Ω

Example Calculation

Given:

  • System: TN-C-S (PME)
  • Ze: 0.35Ω (typical PME value)
  • Circuit: 32A ring final circuit, 2.5mm²/1.5mm² T&E, 40m
  • Protective device: 32A MCB Type B

Step 1: Calculate R1+R2

  • R1 (2.5mm²) = 7.41 mΩ/m, R2 (1.5mm²) = 12.1 mΩ/m
  • R1+R2 = (7.41 + 12.1) x 40 / 1000 = 0.780Ω (at 20°C)

Step 2: Calculate Zs

  • Zs = Ze + (R1+R2) = 0.35 + 0.780 = 1.130Ω

Step 3: Temperature correction

  • Zs (at 70°C) = 0.35 + (0.780 x 1.2) = 0.35 + 0.936 = 1.286Ω

Step 4: Check compliance

  • Max Zs for 32A Type B = 1.37Ω
  • 80% Testing limit = 1.37 x 0.80 = 1.10Ω
  • Calculated Zs (1.130Ω) exceeds 80% limit (1.10Ω) - MARGINAL
  • Temperature-corrected Zs (1.286Ω) within tabulated max (1.37Ω) - technically compliant

Step 5: PEFC

  • PEFC = 230 / 1.130 = 204A

Important Notes

  • Verification: Always verify calculated values by measurement during commissioning. Do not rely solely on calculation.
  • Temperature: R1+R2 values from dead testing are at ambient temperature (~20°C). Under fault conditions at operating temperature, resistance increases by approximately 20% (PVC insulation).
  • TT Systems: In TT installations, Zs is dominated by the earth electrode resistance. RCD protection is mandatory as overcurrent devices cannot provide disconnection within required times.
  • Ring Circuits: For ring final circuits, R1+R2 is approximately one-quarter of the end-to-end readings, not the full cable run.
  • Parallel Paths: Main bonding conductors can provide parallel earth paths that lower the measured Ze. Ensure measurements are taken correctly.

Maximum Zs Values - BS 7671 Table 41.3

These are the maximum permitted earth fault loop impedance values for Type B MCBs in TN systems with a 0.4 second disconnection time. The actual Zs at the furthest point of the circuit must not exceed these values at conductor operating temperature.

MCB RatingType B (max Zs)Type C (max Zs)80% Test Limit (Type B)
6A7.28Ω3.64Ω5.82Ω
10A4.37Ω2.19Ω3.50Ω
16A2.73Ω1.37Ω2.19Ω
20A2.19Ω1.09Ω1.75Ω
32A1.37Ω0.68Ω1.10Ω
40A1.09Ω0.55Ω0.87Ω
50A0.87Ω0.44Ω0.70Ω

Values from BS 7671:2018+A3:2024 Table 41.3. For fuse-protected circuits, refer to Tables 41.2 (BS 88) and 41.4 (BS 3036/BS 1361).

Earthing Systems and Their Effect on Zs

TN-C-S (PME)

The most common system in UK urban areas. The neutral and earth are combined in the supply cable, then separated at the origin.

  • • Typical Ze: 0.20 – 0.35Ω
  • • Maximum declared Ze: 0.35Ω
  • • Low Ze gives generous Zs margin
  • • PME restrictions apply for some installations

TN-S

The earth return path is via the metal sheath of the supply cable. Common in older properties with lead-sheathed cables.

  • • Typical Ze: 0.35 – 0.80Ω
  • • Maximum declared Ze: 0.80Ω
  • • Higher Ze limits maximum cable lengths
  • • No PME risks — good for outbuildings

TT

Earth return via an earth electrode at the property. Common in rural areas with overhead supplies.

  • • Typical Ze: 21 – 200Ω (electrode dependent)
  • • Zs too high for MCB disconnection
  • • RCD protection is mandatory
  • • Ra × IΔn ≤ 50V must be satisfied

Common Earth Fault Loop Questions

What is a good Zs reading?

A “good” Zs reading depends on the protective device. For a 32A Type B MCB (the most common domestic rating), the maximum Zs is 1.37Ω and the 80% testing limit is 1.10Ω. Ideally, your measured Zs should be well below this limit to provide safety margin. In a TN-C-S system with typical Ze of 0.35Ω, most domestic circuits will have Zs values between 0.5Ω and 1.0Ω.

What happens if Zs is too high?

If Zs exceeds the maximum value for the protective device, the fault current during an earth fault will be insufficient to trip the MCB or fuse within the required disconnection time (0.4s for final circuits, 5s for distribution circuits). This means exposed metalwork could remain live at dangerous voltages. It's classified as a C2 code (Potentially Dangerous) on an EICR. Solutions include using larger cable (lower R1+R2), shorter cable run, or adding RCD protection.

How do I measure Ze?

Ze (external earth fault loop impedance) is measured at the origin of the installation with the main earthing conductor disconnected from the MET. This isolates the installation earth from the supply earth so you measure only the supply network impedance. Use a loop impedance tester between line and the supply earth. Warning: disconnecting the main earth removes fault protection from the entire installation — keep testing time to a minimum.

What is PEFC and why does it matter?

PEFC (Prospective Earth Fault Current) is calculated as U0 / Zs (230V / Zs for single-phase). It tells you the fault current that would flow during an earth fault. The protective device must be capable of breaking this current. For a Zs of 1.0Ω, PEFC = 230A. This value must also not exceed the breaking capacity of the MCB (typically 6kA or 10kA for domestic devices — easily satisfied).

Do I use the 80% rule or the temperature correction factor?

Both methods achieve the same result — accounting for conductor heating under fault conditions. The 80% rule is simpler: multiply the tabulated max Zs by 0.80 and compare with your ambient-temperature reading. The correction factor method is more precise: multiply the measured R1+R2 by 1.20 (PVC at 70°C) then add Ze. Use whichever your certification body recommends — NICEIC and NAPIT both accept the 80% method.

Why is Zs different on a TT system?

On a TT system, the earth fault return path goes through the earth electrode, which typically has a resistance of 21Ω or more. This makes Zs far too high for MCBs or fuses to provide disconnection within 0.4 seconds. Instead, TT systems rely on 30mA RCDs for earth fault protection. The RCD detects the imbalance between line and neutral and trips at 30mA regardless of Zs. The requirement becomes Ra × IΔn ≤ 50V (e.g., with a 30mA RCD: Ra ≤ 1667Ω).

Was this calculation helpful?

Complete Calculation Workflow

Follow this workflow for a complete electrical installation calculation: