3-Phase Cable Size Calculator - BS 7671

Calculate cable sizes for 3-phase circuits in commercial and industrial installations per BS 7671:2018+A2:2022

Calculate 3-Phase Cable Size

Enter your 3-phase installation parameters to calculate cable sizes per BS 7671

4-core steel wire armoured cable with PVC insulation (3 phases + neutral) | Table 4D4A

kW

Total power across all three phases (e.g., 30kW motor)

Use 0.85 for motors, 1.0 for resistive loads (heaters, ovens)

metres

One-way distance from distribution board to load

How the cable will be installed (affects current-carrying capacity)

Balanced loads (motors, 3-phase heaters) draw equal current on all phases

3-Phase Cable Sizing - Complete UK Guide

Sizing cables for three-phase circuits requires different calculations to single-phase work. The key difference is the use of the square root of 3 (1.732) factor in current calculations and the use of 3-phase mV/A/m values from BS 7671 Appendix 4 for voltage drop.

Step 1: Calculate Design Current (Ib)

For 3-phase circuits, the line current is calculated from the total power:

I = P / (sqrt(3) x V x pf)

Where P is total power in watts, V is line voltage (400V), and pf is power factor. For example, a 30kW motor with pf of 0.85: I = 30000 / (1.732 x 400 x 0.85) = 50.9A

Step 2: Apply Derating Factors

Calculate the required tabular current by dividing design current by the combined derating factor:

It = Ib / (Ca x Cg x Ci)
  • Ca - Ambient temperature factor (BS 7671 Table 4B1)
  • Cg - Grouping factor (BS 7671 Table 4C1). A 3-phase multicore cable counts as one circuit.
  • Ci - Installation method factor

Step 3: Select Cable from BS 7671 Tables

Use the 3-phase column from the appropriate table:

  • Table 4D4A: SWA cables with PVC insulation (70 degrees C)
  • Table 4E4A: SWA cables with XLPE insulation (90 degrees C)
  • Table 4D1A: Single core cables in conduit/trunking

Select the smallest cable where tabular current rating is greater than or equal to your calculated It.

Step 4: Check Voltage Drop

For 3-phase circuits, use the 3-phase mV/A/m values from BS 7671. These values already account for the square root of 3 factor:

VD = (mV/A/m x I x L) / 1000

The voltage drop limit is 5% of 400V = 20V for power circuits, or 3% = 12V for lighting circuits (BS 7671 Regulation 525).

How 3-Phase Differs from Single Phase

Three-phase power delivers significantly more power than single-phase using less conductor material. Understanding the key differences is essential for correct cable sizing.

Single Phase (230V)

  • Voltage: 230V (Line to Neutral)
  • Current: I = P / (V x pf)
  • Voltage Drop: VD = 2 x I x R x L
  • Conductors: Line + Neutral + Earth
  • Max Power: Typically up to 14kW (60A)
  • Use: Domestic, small commercial

Three Phase (400V)

  • Voltage: 400V (Line to Line)
  • Current: I = P / (sqrt(3) x V x pf)
  • Voltage Drop: VD = (mV/A/m x I x L) / 1000
  • Conductors: 3 Lines + Neutral + Earth
  • Max Power: Hundreds of kW
  • Use: Commercial, industrial, motors

The sqrt(3) Factor Explained

The factor 1.732 (square root of 3) appears because the three phase voltages are separated by 120 electrical degrees. The line-to-line voltage (400V) equals the phase voltage (230V) multiplied by sqrt(3). This same factor reduces the line current compared to single-phase for the same power output, which is why 3-phase systems are more efficient for high-power loads.

Same 30kW Load

1-phase: 130A at 230V

Same 30kW Load

3-phase: 43A at 400V

Conductor Saving

Up to 50% less copper

Common 3-Phase Applications - Cable Size Guide

Typical cable sizes for common 3-phase installations. Always calculate for your specific cable length and installation conditions.

3-Phase Motors

5.5kW (7.5HP): 2.5mm2 SWA, 16A MCCB

11kW (15HP): 4mm2 SWA, 25A MCCB

22kW (30HP): 6mm2 SWA, 50A MCCB

37kW (50HP): 16mm2 SWA, 80A MCCB

55kW (75HP): 25mm2 SWA, 100A MCCB

Use Type D MCBs or MPCB for motor circuits

22kW EV Charger (3-Phase)

Current: 32A per phase

Short run (<25m): 6mm2 4-core SWA

Long run (25-50m): 10mm2 4-core SWA

Protection: 40A Type B RCBO

IET Code of Practice for EV charging applies

Sub-Main Distribution

32A DB: 6mm2 SWA

63A DB: 16mm2 SWA

100A DB: 35mm2 SWA

200A DB: 95mm2 SWA

4-core cable required for unbalanced loads

Commercial Kitchen

Combi Oven (18kW): 6mm2 SWA, 32A

Induction Range (15kW): 4mm2, 25A

Dishwasher (12kW): 4mm2, 20A

Apply CIBSE diversity factors for kitchens

HVAC Systems

Small AC (7kW): 2.5mm2, 16A

Chiller (30kW): 10mm2, 50A

Large AHU (45kW): 16mm2, 80A

Check starting current for voltage drop

Lifts and Escalators

Passenger Lift (15kW): 4mm2, 32A

Goods Lift (30kW): 10mm2, 50A

Escalator (15kW): 4mm2, 25A

Allow for regenerative braking loads

Important: These are typical values for short to medium cable runs with no grouping or elevated temperature derating. Always calculate for your specific installation. Use the calculator above for accurate BS 7671 compliant results.

3-Phase Cable Current Ratings - Quick Reference

Current ratings for common 3-phase cable types at 30 degrees C ambient. Values are for copper conductors. Use derating factors for non-standard conditions.

4-Core SWA PVC Cable (BS 5467) - 3-Phase Ratings

Size (mm2)Clipped/TrayBuried DirectFree AirmV/A/mTypical Use
2.524A36A30A17Small motors, lighting DBs
4.031A44A38A11Small motors, sub-DBs
6.040A56A49A7.322kW EV chargers, small DBs
1054A75A67A4.4Medium motors, DBs
1671A97A88A2.8Large motors, sub-mains
2593A126A115A1.75100A sub-mains
35114A153A141A1.25Large sub-mains
50137A181A170A0.93Main incoming, large DBs
95207A265A256A0.49Main distribution
185308A385A380A0.275Main incoming supply

Reference: BS 7671 Table 4D4A (4-core armoured cable, copper conductors, 70 degrees C PVC)

Worked Example - 30kW Motor Cable Sizing

Scenario:

  • Load: 30kW 3-phase induction motor, power factor 0.85
  • Cable run: 40 metres from main DB
  • Installation: 4-core SWA PVC on cable tray
  • Conditions: 30 degrees C ambient, 3 circuits grouped together

Step 1 - Design Current (Ib):

Ib = 30000 / (1.732 x 400 x 0.85) = 50.9A

Step 2 - Protection Device (In):

Select 63A Type D MCCB (In = 63A, greater than Ib)

Step 3 - Derating Factors:

  • Ca (30 degrees C): 1.0
  • Cg (3 circuits grouped): 0.70
  • Ci (cable tray): 1.0
  • Overall: 1.0 x 0.70 x 1.0 = 0.70

Step 4 - Required Tabular Current (It):

It = 63A / 0.70 = 90A

Step 5 - Cable Selection (Table 4D4A):

25mm2 4-core SWA = 93A on tray (greater than 90A required)

Step 6 - Voltage Drop Check:

From Table 4D4A: 25mm2 = 1.75 mV/A/m (3-phase)

VD = (1.75 x 50.9 x 40) / 1000 = 3.56V

Percentage = (3.56 / 400) x 100 = 0.89% (well within 5% limit)

Final Answer:

Use 25mm2 4-core SWA PVC cable with 63A Type D MCCB. Neutral: 25mm2 (balanced motor, but included in 4-core cable). CPC: Steel wire armour (verify with adiabatic equation) or separate 16mm2 earth.

3-Phase Neutral Sizing - Harmonics and Balance

In a perfectly balanced 3-phase system, the neutral carries zero current. However, modern non-linear loads create harmonic currents that can cause the neutral current to exceed the phase current.

Neutral Sizing Rules (BS 7671 Reg 523.6.3)

ConditionHarmonic ContentNeutral SizeExample
Balanced linear loads<15%Can be reduced (but full size recommended)3-phase motors, heaters
Mixed loads15-33%Same as phase conductorsOffice buildings, retail
Non-linear loads>33%Equal to or greater than phaseData centres, LED arrays

Why Third Harmonics Are Dangerous

Fundamental currents (50Hz) at 120 degrees apart cancel in the neutral. Third harmonic currents (150Hz) are at 3 x 120 = 360 degrees apart, which equals 0 degrees - they are in phase. Instead of cancelling, they add together arithmetically. If each phase has 30% third harmonic content, the neutral can carry current equal to the phase current, even with perfectly balanced phases. This is why modern commercial installations often require full-size or even double-size neutrals.

Best Practice

  • Always use full-size neutrals for distribution board sub-mains
  • Use 4-core cable (not 3-core) unless the load is a balanced motor
  • For data centres and large LED installations, consider double-size neutrals
  • Measure harmonic content with a power quality analyser on existing installations
  • A floating neutral on a 3-phase system can cause 400V on single-phase loads - always protect the neutral connection

Was this calculation helpful?