Max Zs Values Table - BS 7671 Table 41.3

Complete reference table of maximum earth fault loop impedance (Zs) values for UK electrical installations. All values from BS 7671:2018+A2:2022 with 0.8 correction factor applied for ambient temperature measurements.

Understanding the Values

Table values: BS 7671 Table 41.3 values at 70°C conductor temperature.
Measured values (×0.8): Maximum values when testing at ambient temperature (~20°C).
Always use the ×0.8 corrected values when comparing against loop impedance tester readings.

Type B MCB - Max Zs Values (0.4s Disconnection)

Type B MCBs trip at 3-5 times rated current. Used for most domestic and commercial circuits including lighting, socket outlets, and general loads.

Rating (A)Table 41.3 (Ω)×0.8 Measured (Ω)Common Uses
6A7.676.13Lighting circuits
10A4.603.68Lighting, small appliances
16A2.872.30Immersion heaters, radial circuits
20A2.301.84Radial socket circuits, water heaters
32A1.441.15Ring finals, cookers, showers
40A1.150.92Large cookers, EV chargers
50A0.920.74Submains, large loads
63A0.730.58Submains, distribution

Type C MCB - Max Zs Values (0.4s Disconnection)

Type C MCBs trip at 5-10 times rated current. Used for circuits with moderate inrush currents such as fluorescent lighting, small motors, and some commercial equipment.

Rating (A)Table 41.3 (Ω)×0.8 Measured (Ω)Common Uses
6A3.833.07Fluorescent lighting
10A2.301.84Small motors, LED drivers
16A1.441.15Air conditioning, commercial equipment
20A1.150.92Medium motors, transformers
32A0.720.57Larger motors, commercial loads
40A0.570.46Industrial equipment
50A0.460.37Large industrial loads
63A0.360.29Industrial distribution

Type D MCB - Max Zs Values (0.4s Disconnection)

Type D MCBs trip at 10-20 times rated current. Used for circuits with high inrush currents such as transformers, X-ray equipment, and large motors.

Rating (A)Table 41.3 (Ω)×0.8 Measured (Ω)Common Uses
6A1.921.53Small transformers
10A1.150.92Welders, X-ray equipment
16A0.720.57Medium transformers, compressors
20A0.570.46Large motors
32A0.360.29Industrial motors
40A0.290.23Large industrial equipment
50A0.230.18Heavy industrial

BS 88 Fuses - Max Zs Values (5s Disconnection)

BS 88 (BS EN 60269) fuses are typically used for distribution circuits where 5-second disconnection time is acceptable. Values shown are for distribution circuit protection.

Rating (A)Table 41.4 (Ω)×0.8 Measured (Ω)Common Uses
16A3.432.74Small distribution
20A2.552.04Submains protection
32A1.411.13Distribution boards
40A1.040.83Main switch fuses
50A0.780.62Industrial supply
63A0.550.44Main incomer protection
80A0.390.31Large supply protection
100A0.270.22Main supply fuse

Quick Reference - Common Circuit Types

Ring Final Circuit (32A Type B)

Max Zs: 1.44Ω (table) / 1.15Ω (measured)
R1+R2: Typically 0.6-1.0Ω for 2.5mm² T&E

Lighting Circuit (6A Type B)

Max Zs: 7.67Ω (table) / 6.13Ω (measured)
R1+R2: Typically 1.5-3.0Ω for 1.5mm² T&E

Shower Circuit (40A Type B)

Max Zs: 1.15Ω (table) / 0.92Ω (measured)
R1+R2: Typically 0.3-0.5Ω for 10mm² T&E

Cooker Circuit (32A Type B)

Max Zs: 1.44Ω (table) / 1.15Ω (measured)
R1+R2: Typically 0.4-0.7Ω for 6mm² T&E

How to Use the Max Zs Table

1

Identify the protective device

Determine the MCB type (B, C, or D) and rating (Amps) protecting the circuit.

2

Find the ×0.8 corrected value

Look up the corrected value (right column) - this is what your loop impedance tester reading must not exceed.

3

Measure and compare

Use a calibrated loop impedance tester. If measured Zs ≤ table value × 0.8, the circuit complies.

4

Record results

Document the measured Zs value on the Electrical Installation Certificate (Schedule of Test Results).

Need to Calculate Max Zs?

Use our free Max Zs calculator to instantly check compliance for any circuit.

Open Max Zs Calculator →

Frequently Asked Questions